X Start-up and Checkout
Use the following procedure for initial start-up of the boiler:
1) Make sure that the boiler and system are lled with water.
2) Check all new gas piping for leaks and purge piping sections that are lled with air. See the National Fuel Gas Code for
additional information on testing and purging gas lines.
3) Verify that vent system is complete and free of obstructions before attempting to re boiler. Make sure that the silicone cure
time called for in the vent assembly instructions has passed before ring boiler.
4) Inspect all wiring for loose or uninsulated connections.
5) Adjust thermostat to the highest setting.
6) Start the boiler using the lighting instructions on the opposite page.
7) Upon initial start-up, the gas train will be lled with air. Even if the gas line has been completely purged of air, it may take
several tries for ignition before a ame is established. Once a ame has been established for the rst time, subsequent calls
for burner operation should result in a ame on the rst try.
8) Observe pilot burner ame. Pilot burner produces three ames. The center one should be a steady medium blue ame
covering around 3/8” to ½” of spark electrode / ame rod (Figure 42).
9) Inspect the main burner ames visible through the observation port in burner access panel. The ame should be stable and
mostly blue. No yellow tipping should be present; however, intermittent ecks of yellow and orange in the ame are normal
(Figure 43).
10) Check entire gas train for leaks using soap and water or other approved leak detection method while boiler is ring. Fix any
leaks found immediately.
11) Run gas valve safety shutdown test. With main burners ring, disconnect ignition cable from ignition module. Both pilot
burner and main burners should stop ring.
WARNING
• Never attempt to ll a hot empty boiler.
• Never use a ame to check for gas leaks.
• Make sure that the area around the boiler is clear and free from combustible materials, gasoline, and other am-
mable vapors and liquids.
• If antifreeze is used in the system, it must be a nontoxic type such as propylene glycol.
NOTE
Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on the
boiler when the boiler underwent the tests speci ed in Z21.13.