CPG #2561255 FIRELARM 2500 Operating Manual
Order of characters
← key key →
! " # $ % & ' ( ) * + , - . / 0 1 2 3 4 5 6 7 8 9 : ; < = > ? ~
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z [ \ ] ^ _ '
a b c d e f g h i j k l m n o p q r s t u v w x y z { l } ← → (space)
4-5
AC DELAY (HR)?
When an AC trouble condition occurs, the panel will delay the number of hours
programmed under this option. The delay can be set from 6 to 30 hours.
To enter AC trouble reporting delay.
To exit configuration mode.
To skip AC trouble reporting configuration and go to ZDACT
configuration, if used.
To skip AC trouble reporting configuration and go to
password configuration.
AC DELAY (HR):
or To change the value.
To save the value or cancel changes.
SAVE? (Y/N/BACK)
To save changes and advance to password configuration.
To keep previous setting and advance to password
configuration.
To reenter the delay value.
OFFSET TIMER (HR)?
This will set a time delay starting from the entry of the offset timer value for a
phone line check. The check will be performed every 24 hours thereafter. The
24-hour time delay starts from zero on a power cycle of the panel. Keypresses
are similar to AC DELAY (HR)?