Continental BCDV48P Indoor Fireplace User Manual


 
W415-0327 / B / 12.07.07
18
MINIMUM MANTEL AND ENCLOSURE
CLEARANCES
Combustible mantel clearance can vary according to the mantel depth.
Use the graph to help evaluate the clearance needed. Curtains, above
the fi replace, must not be positioned lower than the 2" distance re-
quired for the 2" combustible mantel. These same requirements ap-
ply to any combustibles protruding on either side of the fireplace.
The fi replace requires a minimum enclosure height of 55“. For tempera-
ture requirements, the enclosure space around and above the fi replace
must be left unobstructed.
FIGURE 36
FIGURE 38b
FIGURE 38a
FIGURE 38c
FIGURES 37
* See venting section
Minimum clearance to combustible construction from
replace and vent surfaces:
Framing 0" to stand-offs
Finishing 0" to rear, sides and bottom
Non-combustible fi nishing 8" to top
All around the vent pipe 2"
Recessed depth 23"
Enclosure top 55" from bottom of unit
Clearance to ceiling 84" from bottom of unit