REPLACING FAN
1. Remove motor/guard assembly (follow steps 1 through 4 above).
2. File the setscrew mark off the motor shaft.
3. Replace fan (follow steps 9 through 13 above).
REPLACING ELECTRODE
1. Remove shell and motor/guard assembly (see FAN under maintenance).
2. Pull wire off of electrode.
3. Remove screw holding electrode to diffuser.
4. Remove electrode from diffuser.
5. Place new electrode in diffuser.
6. Install screw, insure electrode gap is .20 (0.5 cm) to .25 (0.6 cm) inch.
7. Push ignitor wire on electrode wire.
8. Reinstall motor/guard assembly and upper shell.
9. For Model 5070A, push ignitor button and check for spark between deflector and elec-
trode. For Model 5075A check for sparks between deflector & electrode after
plugging in. Do not connect propane supply.
Continued
SERVICE
PROCEDURES
Continued
SPECIFICATIONS
FORCED AIR HEATER SPECIFICATIONS
40,000 BTU/HR - MODEL 5070A
Input Rating (BTU/HR) 40,000
Fuel Propane Vapor Only
Fuel Consumption
Gallons/Hour .44 (1.7 L)
Pounds/Hour 1.8 (0.8 kg)
Regulator Output Pressure 10 PSI (70 kPa)
Hose 10 Ft. (3 m)
Hot Air Output (CFM Approx.) 150
Motor 3,000 RPM
Power Required 115 Volt/60 Hz
Amps 1.1
Ignition Manual/Piezo
Weight (pounds) 14 (6.4 kg)
Size (HWL) (IN) 14 x 8.5 x 16.5
(35.6 x 21.6 x 41.9 cm)
Temperature Operating Range -10°F to 85°F
(-23° to 29.4°C)
FORCED AIR HEATER SPECIFICATIONS
50,000 TO 80,000 BTU/HR - MODEL 5075A
Input Rating (BTU/HR) 80,000 Max
Fuel Propane Vapor Only
Fuel Consumption
Gallons/Hour .9 (3.4 L)
Pounds/Hour 3.7 (1.7 kg)
Regulator Output Pressure 10 PSI (70 kPa)
Hose 10 Ft. (3 m)
Hot Air Output (CFM Approx.) 300
Motor 3,000 RPM
Power Required 115 Volt/60 Hz
Amps 2.6
Ignition Electronic Module
Weight (pounds) 17 (7.7 kg)
Size (HWL) (IN) 14 x 8.5 x 22.5
(35.6 x 21.6 x 57.2 cm)
Temperature Operating Range -10°F to 85°F
(-23° to 29.4°C)