D How to check miswiring and serial signal error
• Unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch.
Indoor unit does not operate.
• OPERATION INDICATOR lamp flashes ON and OFF every 0.5-second.
Outdoor unit does not operate.
Turn OFF the power supply.
Is there rated voltage AC in
the power supply?
Yes
No
Turn ON the power supply.
Check the power supply.
Is there rated voltage between
outdoor terminal block S1 and
S2?
No
Check the wiring.
Press EMERGENCY OPERATION switch once.
Does the left lamp of OPERATION INDICATOR
lamp light up? <Con rmation of the power to
the indoor unit>
Yes
No
Is serial signal error indicated 6 minutes later?
Yes
No
Is there any miswiring, poor
contact, or wire disconnec-
tion of the indoor/outdoor
connecting wire?
Is fuse (F65) broken?
Yes
Correct them.
No
A
Turn OFF the power supply.
Check once more if the indoor/outdoor
connecting wire is not miswiring.
Short-circuit outdoor terminal block S2
and S3.
1
B
1. Miswiring may damage indoor electronic control
P.C. board during the operation.
Be sure to con rm the wiring is correct before
the operation starts.
Turn ON the power supply.
Does the LED on the inverter P.C. board or
the outdoor electronic control P.C. board
repeat "3.6-second-OFF and 0.8-second-
ON quick blinking"?
Yes
No
(Lighted
or not
lighted)
Replace the inverter P.C. board or the
outdoor electronic control P.C. board.
2
2. Be careful to the residual
voltage of smoothing capacitor.
Turn OFF the power supply.
Remove the short-circuit between out-
door terminal block S2 and S3.
Turn ON the power supply.
Is there amplitude of 10 to 20 VDC
between outdoor terminal block S2 and
S3? <Con rmation of serial signal>
Yes
No
Is there any error of the in-
door/outdoor connecting wire,
such as the damage of the wire,
intermediate connection, poor
contact to the terminal block?
Yes
Replace the indoor/out-
door connecting wire.
Is there rated voltage between
indoor terminal block S1 and S2?
<Con rmation of power voltage>
No
No
Is there any error of the in-
door/outdoor connecting wire,
such as the damage of the wire,
intermediate connection, poor
contact to the terminal block?
Yes
Replace the indoor/out-
door connecting wire.
No
Replace the indoor electronic control P.C. board.
Yes
Be sure to release the failure-mode recall function
after checking.
Yes
Turn OFF inverter-controlled lighting
equipment.
Turn OFF the power supply and then
turn ON again.
Press EMERGENCY OPERATION
switch.
A
Is serial signal
error indicated 6
minutes later?
B
Yes
Reinstall
either the unit
or the light
each other
away.
Attach a lter
on remote
control receiv-
ing section
of the indoor
unit.
No