2. Indoor unit failure mode table
NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (9-4.).
Left lamp of OP-
ERATION INDICA-
TOR lamp
Abnormal point
(Failure mode)
Condition Correspondence
Not lighted Normal
1-time ash every
0.5-second
Room temperature
thermistor
The room temperature thermistor short or open
circuit is detected every 8 seconds during op-
eration.
Refer to the characteristics of the room temperature
thermistor (9-7.).
2-time ash
2.5-second OFF
Indoor coil thermis-
tor
The indoor coil thermistor short or open circuit
is detected every 8 seconds during operation.
Refer to the characteristics of the main indoor coil
thermistor, the sub indoor coil thermistor (9-7.).
3-time ash
2.5-second OFF
Serial signal
The serial signal from outdoor unit is not re-
ceived for a maximum of 6 minutes.
Refer to 9-6.
"How to check miswiring and serial
signal error".
11-time ash
2.5-second OFF
Indoor fan motor
The rotational frequency feedback signal is
not emit during the 12 seconds the indoor fan
operation.
Refer to 9-6. "Check of indoor fan motor".
12-time ash
2.5-second OFF
Indoor control
system
It cannot properly read data in the nonvolatile
memory of the indoor electronic control P.C.
board.
Replace the indoor electronic control P.C. board.