HEATING CYCLE ANALYSIS
COOLING CYCLE ANALYSIS
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =
FLOW RATE (GPM) x TEMP. DIFF. (DEG. F) x FLUID FACTOR* =
(Btu/hr)
SUPERHEAT = SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE
=
(DEG F)
SUBCOOLING = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE
=
(DEG F)
*Use 500 for water, 485 for antifreeze.
SUCTION
COMPRESSOR
DISCHARGE
COAX
EXPANSION
VALVE
°F
°F
AIR
COIL
°F
PSI
FLUID OUT
FLUID IN
°F
PSI
LOOK UP PRESSURE DROP IN TABLE 31
TO DETERMINE FLOW RATE
°F
LIQUID LINE
PSI
°F
SAT
a50-8494
SUCTION
COMPRESSOR
DISCHARGE
COAX
EXPANSION
VALVE
°F
°F
AIR
COIL
°F
PSI
FLUID OUT
FLUID IN
°F
PSI
LOOK UP PRESSURE DROP IN TABLE 31
TO DETERMINE FLOW RATE
°F
LIQUID LINE
PSI
°F
SAT
a50-8495