APPENDIX A — WSHP OPEN SCREEN CONFIGURATION
LEGEND
SCREEN NAME POINT NAME
PASSWORD
LEVEL
EDITABLE RANGE DEFAULT NOTES
Equipment
Status
Operating Mode
No Password
Required
Off, Fan Only, Economize,
Cooling, Heating, Cont Fan,
Test, Start Delay, Dehumidify
Displays unit operating mode
SPT F Displays SPT
SAT F Displays SAT
Condenser Leaving
Temperature
F
Displays leaving condenser
water temperature
Condenser Entering
Temperature
F
Displays entering condenser
water temperature (Value
will not update when compressor
is operating)
Fan
Off/Low Speed/
Medium Speed
High Speed/On
Displays fan speed status
Compressor Capacity 0 - 100% Displays compressor capacity
Damper Position 0 - 100%
Displays current damper position
(Viewable only if Ventilation DMP
Type = 2 position or DCV)
H
2
O Economizer 0 - 100% Displays position of economizer valve
Auxiliary Heat 0 - 100%
Displays position of auxiliary
reheat valve (Viewable only if Leaving
Air Auxiliary Heat Type = 2 position,
1 stage Elect or Modulating)
Space RH 0 - 100%
Displays space RH% (Viewable only if
Humidity Sensor = Installed)
Dehumidification Inactive/Active
Displays if dehumidification is active
(Viewable only if Factory
Dehumidification Reheat = Installed)
IAQ CO
2
0 - 9999 ppm Displays the space CO
2
level
Alarm Status
SPT Alarm Status
No Password
Required
Normal/Alarm
Displays current space
temperature condition
Alarming SPT F
Displays the SPT that
exceeded the alarm limit (when SPT
alarm above is in Alarm)
SPT Alarm Limit F
Displays the SPT alarm limit that was
exceeded; causing the alarm condition
(when SPT alarm above is in Alarm)
SPT Sensor Alarm
Status
Normal/Alarm
Displays the status of the Rnet
SPT sensor - ALARM is displayed
should the sensor fail to communicate
with the control module
IAQ Alarm Status Normal/Alarm Current IAQ/ventilation condition
Compressor Alarm
Status
Normal/Alarm Current compressor condition
SAT Alarm Status Normal/Alarm Current SAT condition
Condensate Overflow
Alarm Status
Normal/Alarm
Current status of the condensate
drain (overflow switch)
Condenser Water Tem-
perature Alarm Status
Normal/Alarm
Current status of the
condenser water
Filter Alarm Status Normal/Alarm Current filter condition
Space RH Alarm Status Normal/Alarm Current space RH condition
OAT Alarm Status Normal/Alarm
Current status of the OAT
broadcast function
Airside Linkage Status Normal/Alarm Current linkage status if enabled
Condenser Water
Linkage
Normal/Alarm Current linkage status if enabled
Sensor
Calibration
SAT
Admin Password
level access only
F Display SAT
SAT Offset X -9.9 - 10.0 F 0 F Used to correct sensor reading
Leaving Condenser
Water Temperature
F
Displays Leaving Condenser
Water Temperature
Leaving CW Offset X -9.9 - 10.0 F 0 F Used to correct sensor reading
Rnet Sensor
Temperature
F Displays SPT
Rnet Offset X -9.9 - 10.0 F 0 F Used to correct sensor reading
RH % Displays Space RH value
RH Sensor Offset X -15% - 15% 0 % Used to correct sensor reading
°
°
°
°
°
°
°
°°
°
°°
°
°°
BAS Building Automation System
DCV Demand Controlled Ventilation
IAQ Indoor Air Quality
OAT Outdoor Air Temperature
RH Relative Humidity
SAT Supply Air Temperature
SPT Space Temperature
TPI Third Party Integration