Carrier PSD006-070 Heat Pump User Manual


 
37
Table 22 — 50PSH, PSV, PSD012 Typical Unit Operating Pressures and Temperatures
LEGEND
Table 23 — 50PSH, PSV, PSD018 Typical Unit Operating Pressures and Temperatures
LEGEND
Table 24 — 50PSH, PSV, PSD024 Typical Unit Operating Pressures and Temperatures
LEGEND
ENTERING
WATER
TEMP
(F)
WATER
FLOW
(GPM/ton)
FULL LOAD COOLING — WITHOUT HWG ACTIVE FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Rise
(F)
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Drop
(F)
Air Temp
Rise
(F) DB
30
1.5 98-108 140-160 36-41 14-19 17.1-19.1 19-25 72-82 301-321 9-14 12-17 6.5-8.5 21-27
2.25 98-108 135-155 36-41 12-17 12.5-14.5 19-25 85-95 304-324 9-14 12-17 4.7-6.7 21-27
3 99-109 127-148 36-41 10-15 7.9-9.9 19-25 78-88 308-328 9-14 12-17 2.9-4.9 22-28
50
1.5 118-128 215-235 22-27 14-19 18.1-20.1 20-26 100-110 337-357 10-15 15-20 9.5-11.5 26-32
2.25 118-128 200-220 22-27 12-17 13.1-15.1 20-26 98-108 334-354 10-15 15-20 6.6-8.6 26-32
3 118-128 185-205 22-27 10-15 8.1-10.1 19-25 95-105 332-352 11-16 15-20 3.8-5.8 26-32
70
1.5 132-142 300-320 11-16 12-17 17.0-19.0 19-25 115-125 361-381 19-24 18-23 11.1-13.1 29-35
2.25 132-142 263-282 11-16 10-15 12.6-14.6 19-25 112-122 360-380 20-25 18-23 8.0-10.0 29-35
3 132-142 245-265 12-17 7-12 8.2-10.2 19-25 110-120 356-376 21-26 18-23 4.8-6.8 29-35
90
1.5 138-148 366-386 9-14 11-16 15.8-17.8 18-24 122-132 376-396 34-39 22-27 12.1-14.1 32-38
2.25 138-148 353-373 9-14 9-14 14.9-16.9 18-24 123-133 378-398 36-41 22-27 9.0-11.0 32-38
3 138-148 340-360 9-14 6-11 14.0-16.0 18-24 124-134 380-400 38-43 23-28 5.8-7.8 32-38
110
1.5 145-155 453-473 9-14 9-14 14.7-16.7 16-22
2.25 145-155 442-462 9-14 7-12 10.8-12.8 16-22
3 145-155 431-451 9-14 5-10 6.8-8.8 17-23
DB Dry Bulb
HWG Hot Water Generator
——No Heating Operation in This Temperature Range
ENTERING
WATER
TEMP
(F)
WATER
FLOW
(GPM/ton)
FULL LOAD COOLING — WITHOUT HWG ACTIVE FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Rise
(F)
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Drop
(F)
Air Temp
Rise
(F) DB
30
1.5 120-130 155-175 27-32 11-16 16.9-19.9 16-22 73- 83 268-288 8-13 4- 9 6.1- 8.1 15-21
2.25 120-130 142-162 27-32 9-14 12.5-14.5 17-23 75- 85 270-290 8-13 4- 9 4.4- 6.4 16-22
3 120-130 128-148 27-32 9-14 8.1-10.1 17-23 78- 88 272-292 8-13 4- 9 2.9- 4.9 16-22
50
1.5 137-147 220-240 16-21 10-15 17.0-19.0 16-22 102-112 295-315 8-13 8-13 9.1-11.1 20-26
2.25 137-147 206-226 16-21 8-13 12.6-14.6 17-23 106-116 297-317 8-13 8-13 6.9- 8.9 21-27
3 137-147 192-212 16-21 8-13 8.4-10.4 17-23 110-120 299-319 8-13 8-13 4.7- 6.7 21-27
70
1.5 142-152 287-307 7-12 10-15 15.9-17.9 16-22 131-141 324-344 9-14 10-15 12.1-14.1 25-33
2.25 142-152 273-239 7-12 8-13 11.8-13.8 17-23 137-147 326-346 9-14 10-15 9.3-11.3 26-34
3 142-152 259-279 7-12 8-13 7.8- 9.8 17-23 144-154 328-348 9-14 10-15 6.6- 8.6 26-34
90
1.5 146-156 375-395 6-11 10-15 14.9-16.9 16-22 174-184 360-380 10-15 12-17 15.8-17.8 32-40
2.25 146-156 361-381 6-11 8-13 11.0-13.0 17-23 180-190 367-387 11-16 12-17 11.9-13.9 33-41
3 146-156 347-367 6-11 8-13 7.2- 9.2 17-23 187-197 374-394 12-17 12-17 8.0-10.0 33-41
110
1.5 154-164 478-498 6-11 10-15 14.0-16.0 16-22
2.25 154-164 461-481 6-11 8-13 10.2-12.2 16-22
3 154-164 445-465 6-11 8-13 6.5- 8.5 16-22
DB Dry Bulb
HWG Hot Water Generator
——No Heating Operation in This Temperature Range
ENTERING
WATER
TEMP
(F)
WATER
FLOW
(GPM/ton)
FULL LOAD COOLING — WITHOUT HWG ACTIVE FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Rise
(F)
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Drop
(F)
Air Temp
Rise
(F) DB
30
1.5 115-125 154-174 40-45 8-13 16.5-18.5 19-25 73- 83 283-303 8-12 6-11 5.9- 7.9 16-22
2.25 115-125 141-161 40-45 6-11 12.1-14.1 20-26 75- 85 285-305 8-12 6-11 4.2- 6.2 17-23
3 115-125 127-147 40-45 6-11 77.7- 9.7 20-26 78- 88 287-307 8-12 6-11 2.7- 4.7 18-24
50
1.5 115-120 209-229 24-29 10-15 15.7-17.7 18-24 102-112 313-333 8-12 8-13 8.9-10.9 22-28
2.25 115-120 195-215 24-29 8-13 11.6-13.6 18-24 106-116 314-334 8-12 8-13 6.7- 8.7 23-29
3 115-120 181-201 24-29 8-13 7.6- 9.6 18-24 110-120 316-336 8-12 8-13 4.5- 6.5 23-29
70
1.5 136-146 275-295 6-11 6-11 15.7-17.7 18-24 128-138 340-360 9-14 9-14 11.3-13.3 27-34
2.25 136-146 261-281 6-11 5-10 11.6-13.6 18-24 134-144 342-362 9-14 9-14 8.5-10.5 28-35
3 136-146 247-267 6-11 4- 9 7.6- 9.6 18-24 141-151 344-364 9-14 9-14 5.8- 7.8 28-35
90
1.5 140-150 361-381 6-11 6-11 14.9-16.9 18-24 162-172 370-390 14-19 9-14 14.4-16.4 32-40
2.25 140-150 347-367 6-11 5-10 11.0-13.0 18-24 166-176 376-396 15-20 9-14 10.8-12.8 34-42
3 140-150 333-353 6-11 4- 9 7.2- 9.2 18-24 171-181 383-403 16-21 9-14 7.1- 9.1 34-42
110
1.5 144-154 460-480 6-11 6-11 13.9-15.9 17-23
2.25 144-154 445-465 6-11 4- 9 10.2-12.2 17-23
3 144-154 428-448 6-11 4- 9 6.5- 8.5 17-23
DB Dry Bulb
HWG Hot Water Generator
——No Heating Operation in This Temperature Range