Carrier 50RLP Heat Pump User Manual


 
27
OCCUPIED FROM — This field is used to configure the
hour and minute, in military time, that the mode for the
PremierLink™ controller will switch to occupied.
Occupied From: Units Hours:Minutes
Range 00:00 to 24:00
(Minutes 00 to 59)
Default Value 00:00
OCCUPIED TO — This field is used to configure the hour
and minute, in military time, that the mode for the PremierLink
controller switches from occupied to unoccupied.
Occupied To: Units Hours:Minutes
Range 00:00 to 24:00
(Minutes 00 to 59)
Default Value 24:00
Table 21 Occupancy Schedule (OCCPC01)
*User configured.
Network Time Schedule
The network time schedule
allows the occupancy schedule in another device on the CCN
to control the Aquazone™ system control panel’s occupancy
state.
Each time the occupancy schedule on the controlling device
changes to occupied, the controlling device broadcasts an
occupancy flag over the CCN. To receive an occupancy flag,
a network time created. Up to 18 network time schedules are
configured. The schedules are sequentially named OCCPC65E
to OCCPC82E, however Service Tool or Building Supervisor
software can be used to modify the names up to OCCPC99E.
Holiday Schedules
A Holiday schedule allows the
user the capability to specify days of the year (holidays) on
which the Aquazone system control panel will follow the
holiday time schedule instead of the normal time schedule for
that day. Holiday time schedules are normally used to program
a weekday in unoccupied mode for the entire day since the
building will be empty during a holiday.
There are 16 different holiday schedules that can be created.
Holiday schedules can also last more than one day, as long as
the days are consecutive.
Holiday schedules must be configured on the time and date
broadcaster element on the CCN. If the Comfort Controller on
the Aquazone system control panel is the broadcaster, it will
send holiday status to all other system elements on the CCN. If
the Comfort Controller is not the broadcaster, do not configure
the holiday schedules for it, as they will not be used.
To configure a holiday schedule, enter a “1” in the Holiday
column of the Day of Week point of the Occupancy schedule.
DESCRIPTION VALUE NAME
Time Schedule
Manual Override Hours
0 hours Ovrd
Period 1: Day of Week
00000000 DOW1
Period 1: Occupied from
00:00 Occ1
Period 1: Occupied to
24:00 UnOcc1
Period 2: Day of Week
00000000 DOW2
Period 2: Occupied from
00:00 Occ2
Period 2: Occupied to
24:00 UnOcc2
Period 3: Day of Week
00000000 DOW3
Period 3: Occupied from
00:00 Occ3
Period 3: Occupied to
24:00 UnOcc3
Period 4: Day of Week
00000000 DOW4
Period 4: Occupied from
00:00 Occ4
Period 4: Occupied to
24:00 UnOcc4
Period 5: Day of Week
00000000 DOW5
Period 5: Occupied from
00:00 Occ5
Period 5: Occupied to
24:00 UnOcc5
Period 6: Day of Week
00000000 DOW6
Period 6: Occupied from
00:00 Occ6
Period 6: Occupied to
24:00 UnOcc6
Period 7: Day of Week
00000000 DOW7
Period 7: Occupied from
00:00 Occ7
Period 7: Occupied to
24:00 UnOcc7
Period 8: Day of Week
00000000 DOW8
Period 8: Occupied from
00:00 Occ8
Period 8: Occupied to
24:00 UnOcc8
Push Button Override
LATCHI00 Name*
Thermostat Override
TEMP_I00 Name*
Time Delay
5 min Value*
Timed Override Duration
5 min Value*
Power on Delay
0 sec PowerUp