Carrier 50RLP Heat Pump User Manual


 
11
PREMIERLINK™ CONTROLLER INPUTS AND OUT-
PUTS — When PremierLink controllers are factory mounted
with water source heat pump equipment to implement a CCN
system installation, the inputs and outputs are shown in Table 3.
CONNECT POWER The Aquazone™ system control
panel requires an uninterrupted 110-v, single-phase, 60 Hz
power supply. All field wiring must comply with all local and
national fire, safety and electrical codes. It is recommended
that the power supply be separate from the power source
supplying the water source heat pumps. The Aquazone system
control panel is internally fused and a power switch is located
inside the enclosure. Supply power to the Aquazone system
control panel through the convenience outlet in the bottom left
hand corner of the Aquazone system control panel. Do not
apply power until all connections have been made and voltage
supply has been verified. Ground in accordance with NEC and
local electrical codes. Connect the dedicated ground wire to the
position in relationship to the main supply line and use shield
cable to protect from any electrical interference.
CONTROL WIRING — Low voltage wiring for the Aqua-
zone system control panel is shown in Fig. 8.
Table 3 PremierLink Controller Inputs and Outputs
LEGEND
INPUTS POWER TERMINAL(S)
SPACE TEMPERATURE (SPT)
AI (10 K Thermistor) J6-7, J6-6
SET POINT ADJUSTMENT (STO)
AI (10 K Thermistor) J6-5, J6-6
SUPPLY AIR TEMPERATURE (SAT)
AI (10 K Thermistor) J6-3, J6-4
LEAVING WATER TEMPERATURE
AI (10 K Thermistor) J6-1, J6-2
IAQ SENSOR (IAQI)
(4-20 mA) J5-5, J5-6
REMOTE TIME CLOCK (RMTOCC)
DI (24 vac) J4-11, J4-12
COMPRESSOR LOCKOUT (CMPSAFE)
DI (24 vac) J4-9, J4-10
FIRE SHUTDOWN (FSD)
DI (24 vac) J4-7, J4-8
SUPPLY FAN STATUS (SFS)
DI (24 vac) J4-5, J4-6
NOT USED
——
OUTPUTS POWER TERMINALS
FAN (SF)
DO Relay (24 vac, 1A) J8-18
COOL STAGE 1 (CMP1)
DO Relay (24 vac, 1A) J8-15
COOL STAGE 2 (CMP2)
DO Relay (24 vac, 1A) J8-12
HEAT STAGE 1 (HS1)
DO Relay (24 vac, 1A) J8-9
HEAT STAGE 2 (HS2)
DO Relay (24 vac, 1A) J8-6
HEAT 3/EXHAUST/REVERSING VALVE (HS3/EXH/RVS)
DO Relay (24 vac, 1A) J8-3
AI
Analog Input
DI
Digital Input
DO
Digital Output