BOILER/HEAT SOURCE CONTROL TYPE — This con-
figuration determines how the tower outputs will be controlled.
If panels were ordered with the stage output transducers, then
tower control type should be set to 0. If the tower outputs will
control variable speed tower fans, then the configuration
should be set to 1.
Variable speed configuration will control both outputs
simultaneously.
Boiler/Heat Source Control Type:
Configuration Units None
Configuration Range 0 or 1
Default Value 0
GLOBAL SCHEDULE BROADCAST — If desired, the
schedules 1 through 18 in the Aquazone™ system control
panel may be reconfigured to be schedules 65 through 82 (so
that they may be used as global schedules). If this is done, this
configuration must be set to 1. Local inputs for overriding
zones 1 to 18 or the remote occupancy input will then affect the
global schedules 65 through 82. In this condition local override
of individual PremierLink™ controllers will not occur since
the comfort controller does not respond to the command from
any PremierLink controller to override a global schedule. It is
recommended to allow the PremierLink controllers to broad-
cast global schedules.
Fig. 11 Loop Supply Water Set Point Screen
Fig. 12 System Pressure Set Point Screen