Carrier 50RLP Heat Pump User Manual


 
13
LEGEND FOR FIG. 8
Install Thermostat, Sensors and Switches
In
all installations, the loop supply water temperature sensor and
water flow switch must be installed in the field. The water
pressure sensor is used to sense water system pressure to
operate in conjunction with pump variable frequency drives.
A thermostat is used in stand-alone systems. A space tempera-
ture sensor is used in conjunction with water source heat
pumps provided with PremierLink™ controllers. Refer to the
accessory installation instructions literature provided with each
accessory that is used for accessory installation instructions.
NOTE: All thermostats, sensors, and switches are field-
installed accessories.
Install Loop Water Supply and Return Tem-
perature Sensors
Install the water loop supply sen-
sor in the main water supply, located before the water source
heat pumps. Install the water loop return sensor in the return
water piping from the water source heat pumps. The sensors
must be inserted fully into an immersion well (provided). Seal
immersion well threads with tape and install into pipe tee or re-
ducing fitting. The well screws into a
1
/
2
-in. NPT saddle (or
Thredolet fitting) furnished by the installing contractor. Screw
the sensor into the well via the
1
/
8
-in. NPT brass fitting. Termi-
nate wiring with butt splice or soldering. Wire nuts are not rec-
ommended. Use full 8 ft of lead length provided to avoid mois-
ture migration up the wire. Wire the supply sensor to terminals
SSWT. Wire the return sensor to terminals SRWT. See Fig. 8.
Sensors may be located in any position in relationship to the
main supply line. Use shield cable to protect from any electri-
cal interference.
Install Loop Water Pressure Sensor
Install the
pressure sensor on the discharge side of the circulating pump(s)
in a common supply main so that total system pressure rather
than individual pump(s) flow is detected. The pressure sensor
must be placed in a vertical position and must match the actual
water flow direction with flow switch direction indicators. Seal
the switch fitting with Teflon tape and insert in a
1
/
4
-in.
standard pipe tee (Thredolet fitting) or reducing fitting, with at
least three pipe diameters straight run upstream and down-
stream of the switch. Wire sensor to terminals SDP. See Fig. 8.
Install Loop Water Flow Switch
Install the loop
water flow switch on the discharge side of the circulating
pump(s) in a common supply main so that total system flow
rather than individual pump(s) flow is detected. The flow
switch must be placed in a vertical position and must match the
actual water flow direction with flow switches direction indica-
tors. Seal the switch fitting with Teflon tape and insert in a stan-
dard pipe tee or reducing fitting, with at least three pipe diame-
ters straight run upstream and downstream of the switch.
Electrical connection can be made to the switch. Two wires
should be run to the switch for 24 VAC power. The switch is
supplied with wire leads for connection to the FLOW terminal.
When power is supplied to the device, a warm-up period is
initiated. During this period, the right green LED will be lit.
Each LED to the left is successively lit until the farthest left red
LED is lit. Each LED will be turned off when the next is lit.
The warm-up period may take up to 30 seconds.
When flow is detected, a red LED at the far left will be lit.
With increasing flow, successive red LEDs will be lit. When
the switch determines sufficient flow is present, the amber
LED lights indicating the output has closed. This is not an indi-
cation of minimum flow. As flow increases, the first green
LED will be lit. Each successive green LED indicates greater
flow. The switch closure does not indicate minimum flow for
the machine. With one green LED lit, minor fluctuations in
water flow may cause nuisance alarms. Additional green LEDs
indicate higher flow rates, and can avoid the nuisance alarms.
The switch is calibrated to light the amber LED at a fluid
velocity of 0.8 ft/sec (0.24 m/sec). The flow rate will depend on
the nozzle size. See Table 4. See Table 5 for Water Flow
Switch Troubleshooting. If the water flow switch is not work-
ing correctly, refer to Table 5.
Table 4 Loop Water Flow Switch LED Display
ALLSYS
System
BLRL1
Heat Source 1 Speed/Level
BLRL2
Heat Source 2 Speed/Level
CB
Circuit Breaker
CTL1
Cooling Tower 1 Speed/Level
CTL2
Cooling Tower 2 Speed/Level
FLOW
Loop Water Flow
OVRIZ1
Override Input for Zone 1
OVRIZ2
Override Input for Zone 2
OVRIZ3
Override Input for Zone 3
OVRIZ4
Override Input for Zone 4
OVRIZ5
Override Input for Zone 5
OVRIZ6
Override Input for Zone 6
OVRIZ7
Override Input for Zone 7
OVRIZ8
Override Input for Zone 8
OVRIZ9
Override Input for Zone 9
OVRIZ10
Override Input for Zone 10
OVRIZ11
Override Input for Zone 11
OVRIZ12
Override Input for Zone 12
OVRIZ13
Override Input for Zone 13
OVRIZ14
Override Input for Zone 14
OVRIZ15
Override Input for Zone 15
OVRIZ16
Override Input for Zone 16
OVRIZ17
Override Input for Zone 17
OVRIZ18
Override Input for Zone 18
PCB
Comfort Controller Circuit Board
PUMP1
Pump Number 1
PUMP2
Pump Number 2
RMTOCC
Remote Occupied Mode
SDP
System Differential Pressure
SRWT
System Return Water Temperature
SSWT
System Supply Water Temperature
SYSZ1
System for Zone 1
SYSZ2
System for Zone 2
SYSZ3
System for Zone 3
SYSZ4
System for Zone 4
SYSZ5
System for Zone 5
SYSZ6
System for Zone 6
SYSZ7
System for Zone 7
SYSZ8
System for Zone 8
SYSZ9
System for Zone 9
SYSZ10
System for Zone 10
SYSZ11
System for Zone 11
SYSZ12
System for Zone 12
SYSZ13
System for Zone 13
SYSZ14
System for Zone 14
SYSZ15
System for Zone 15
SYSZ16
System for Zone 16
SYSZ17
System for Zone 17
SYSZ18
System for Zone 18
T
Transformer
TB
Terminal Block
TBP
Terminal Block or Pin Connector
SIZE
SCHEDULE 40 PIPE
O.D. (in.) Wall Thickness (in.) I.D. (in.) Area (Ft
2
)GPM
4
4.5 .237 4.026 0.09 32
5
5.563 .258 5.047 0.14 50
6
6.625 .28 6.065 0.20 72
8
8.625 .322 7.981 0.35 125