Table 1 — Electrical Data — Units Without Optional Powered Convenience Outlet
UNIT
50PG
NOMINAL
POWER
SUPPLY
VOLTS−PH−HZ
VOLTAGE
RANGE
COMPRESSOR
(EA)
OFM
FLA
IFM
FLA
POWER
EXHAUST
FLA
IFM
TYPE
ELECTRIC HEAT POWER SUPPLY
CRSINGLE
PART
NO.
(N
ote 3)
DISCONNECT
SIZE
WIRING
FIG.
NO.
MIN MAX RLA LRA
CRHEATER
PART
NO.
FLA
NOMINAL
KW*
MCA MOCP{ FLA LRA
03 208/230-1-60 187 253 12.8 60 0.9 4.9
Ċ
Low
Ċ Ċ Ċ/Ċ 21.8/21.8 30/30 Ċ 21/21 73/73 Ċ
200A00 10.8/12.5 2.3/3.0 21.8/21.8 30/30 028A00 21/21 73/73 13
201A00 17.3/20.0 3.8/5.0 27.8/31.1 30/35 028A00 26/29 73/73 13
202A00 26.0/30.0 5.6/7.5 38.6/43.6 40/45 028A00 36/40 73/73 13
203A00 34.7/40.0 7.5/10.0 49.5/56.1 50/60 028A00 45/52 73/73 13
High
Ċ Ċ Ċ/Ċ 21.8/21.8 30/30 Ċ 21/21 73/73 Ċ
200A00 10.8/12.5 2.3/3.0 21.8/21.8 30/30 028A00 21/21 73/73 13
201A00 17.3/20.0 3.8/5.0 27.8/31.1 30/35 028A00 26/29 73/73 13
202A00 26.0/30.0 5.6/7.5 38.6/43.6 40/45 028A00 36/40 73/73 13
203A00 34.7/40.0 7.5/10.0 49.5/56.1 50/60 028A00 45/52 73/73 13
1.4
Low
Ċ Ċ Ċ/Ċ 23.2/23.2 30/30 Ċ 23/23 75/75 Ċ
200A00 10.8/12.5 2.3/3.0 23.2/23.5 30/30 028A00 23/23 75/75 13
201A00 17.3/20.0 3.8/5.0 29.5/32.9 30/35 028A00 27/30 75/75 13
202A00 26.0/30.0 5.6/7.5 40.4/45.4 45/50 028A00 37/42 75/75 13
203A00 34.7/40.0 7.5/10.0 51.2/57.9 60/60 028A00 47/53 75/75 13
High
Ċ Ċ Ċ/Ċ 23.2/23.2 30/30 Ċ 23/23 75/75 Ċ
200A00 10.8/12.5 2.3/3.0 23.2/23.5 30/30 028A00 23/23 75/75 13
201A00 17.3/20.0 3.8/5.0 29.5/32.9 30/35 028A00 27/30 75/75 13
202A00 26.0/30.0 5.6/7.5 40.4/45.4 45/50 028A00 37/42 75/75 13
203A00 34.7/40.0 7.5/10.0 51.2/57.9 60/60 028A00 47/53 75/75 13
04
208/230-1-60 187 253 15.4 83 0.9 4.9
Ċ
Low
Ċ Ċ Ċ/Ċ 25.0/25.0 30/30 Ċ 24/24 96/96 Ċ
200A00 10.8/12.5 2.3/3.0 25.0/25.0 30/30 028A00 24/24 96/96 13
201A00 17.3/20.0 3.8/5.0 27.8/31.1 30/40 028A00 26/29 96/96 13
202A00 26.0/30.0 5.6/7.5 38.6/43.6 40/45 028A00 36/40 96/96 13
203A00 34.7/40.0 7.5/10.0 49.5/56.1 50/60 028A00 45/52 96/96 13
204A00 52.0/60.0 11.3/15.0 71.1/81.1 80/90 029A00 65/75 96/96 14
High
Ċ Ċ Ċ/Ċ 25.0/25.0 30/30 Ċ 24/24 96/96 Ċ
200A00 10.8/12.5 2.3/3.0 25.0/25.0 30/30 028A00 24/24 96/96 13
201A00 17.3/20.0 3.8/5.0 27.8/31.1 30/40 028A00 26/29 96/96 13
202A00 26.0/30.0 5.6/7.5 38.6/43.6 40/45 028A00 36/40 96/96 13
203A00 34.7/40.0 7.5/10.0 49.5/56.1 50/60 028A00 45/52 96/96 13
204A00 52.0/60.0 11.3/15.0 71.1/81.1 80/90 029A00 65/75 96/96 14
1.4
Low
Ċ Ċ Ċ/Ċ 26.4/26.4 40/40 Ċ 26/26 98/98 Ċ
200A00 10.8/12.5 2.3/3.0 26.4/26.4 40/40 028A00 26/26 98/98 13
201A00 17.3/20.0 3.8/5.0 29.5/32.9 40/40 028A00 27/30 98/98 13
202A00 26.0/30.0 5.6/7.5 40.4/45.4 45/50 028A00 37/42 98/98 13
203A00 34.7/40.0 7.5/10.0 51.2/57.9 60/60 028A00 47/53 98/98 13
204A00 52.0/60.0 11.3/15.0 72.9/82.9 80/90 029A00 67/76 98/98 14
High
Ċ Ċ Ċ/Ċ 26.4/26.4 40/40 Ċ 26/26 98/98 Ċ
200A00 10.8/12.5 2.3/3.0 26.4/26.4 40/40 028A00 26/26 98/98 13
201A00 17.3/20.0 3.8/5.0 29.5/32.9 40/40 028A00 27/30 98/98 13
202A00 26.0/30.0 5.6/7.5 40.4/45.4 45/50 028A00 37/42 98/98 13
203A00 34.7/40.0 7.5/10.0 51.2/57.9 60/60 028A00 47/53 98/98 13
204A00 52.0/60.0 11.3/15.0 72.9/82.9 80/90 029A00 67/76 98/98 14
208/230-3-60 187 253 11.5 77 0.9 4.9 Ċ
Low
Ċ Ċ Ċ/Ċ 20.2/20.2 30/30 Ċ 20/20 90/90 Ċ
207A00 6.3/7.2 2.3/3.0 20.2/20.2 30/30 030A00 20/20 90/90 15
208A00 10.0/11.5 3.8/5.0 20.2/20.6 30/30 030A00 20/20 90/90 15
209A00 15.0/17.3 5.6/7.5 24.9/27.8 30/30 030A00 23/26 90/90 15
210A00 20.0/23.1 7.5/10.0 31.1/35.0 35/40 030A00 29/32 90/90 15
211A00 30.0/34.6 11.3/15.0 43.6/49.4 45/50 030A00 40/45 90/90 15
High
Ċ Ċ Ċ/Ċ 20.2/20.2 30/30 Ċ 20/20 90/90 Ċ
207A00 6.3/7.2 2.3/3.0 20.2/20.2 30/30 030A00 20/20 90/90 15
208A00 10.0/11.5 3.8/5.0 20.2/20.6 30/30 030A00 20/20 90/90 15
209A00 15.0/17.3 5.6/7.5 24.9/27.8 30/30 030A00 23/26 90/90 15
210A00 20.0/23.1 7.5/10.0 31.1/35.0 35/40 030A00 29/32 90/90 15
211A00 30.0/34.6 11.3/15.0 43.6/49.4 45/50 030A00 40/45 90/90 15
LEGEND
FLA − Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
IFM Indoor − Fan Motor
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
NEC National Electrical Code
OFM Outdoor−Fan Motor
RLA Rated Load Amps
* Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribu-
tion voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equip-
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than
2%. Use the following formula to determine the percentage of voltage imbalance.
% Voltage Imbalance = 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
224 + 231 + 226
3
681
3
=
227
=
Determine maximum deviation from average voltage.
(AB) 227 – 223 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
4
227
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. Single point kits CRSINGLE028A00 and CRSINGLE030A00 are not required if
field−supplied pressure connectors are used.
50PG03−16