Carrier 33ZCVAVTRM Air Conditioner User Manual


 
36
Table 7 Occupancy Schedule Information Screen
If a 1 is configured in the corresponding place for a certain
day of the week, the related Occupied from and Occupied
to times for that period will take effect on that day of the
week. If a 1 is placed in the holiday field the related times will
take effect on a day configured as a holiday. A zero means the
schedule period will not apply to that day.
Period (1-8):
Day of Week: Range 0 or 1
Default Values 11111111 for period 1,
00000000 for periods 2-8.
Occupied From
This field is used to configure the hour and
minute, in military time, when the mode for the zone controller
becomes occupied.
Period (1-8):
Occupied from: Units Hours: Minutes
Range 00:00 to 24:00
Default Value 00:00
Occupied To
This field is used to configure the hour and
minute, in military time, when the occupied mode for the zone
controller becomes unoccupied.
Period (1-8):
Occupied from: Units Hours: Minutes
Range 00:00 to 24:00
Default Value 24:00
SET POINT SCREEN The Set Point screen is used to
modify the zone controller set points. See Table 8.
Occupied Heat
The Occupied Heat set point is used to con-
figure the heating set point for the zone controller during Occu-
pied mode.
Occupied Heat: Units F (C)
Range 40.0 to 90.0
Default Value 70.0
Occupied Cool
The Occupied Cool set point is used to con-
figure the cooling set point for the zone controller during Occu-
pied mode.
Occupied Cool: Units F (C)
Range 45.0 to 99.9
Default Value 74.0
Unoccupied Heat
The Unoccupied Heat set point is used to
configure the heating set point for the zone controller during
Unoccupied mode.
Unoccupied Heat: Units F (C)
Range 40.0 to 90.0
Default Value 55.0
Unoccupied Cool
The Unoccupied Cool set point is used to
configure the cooling set point for the zone controller during
Unoccupied mode.
Unoccupied Cool: Units F (C)
Range 45.0 to 99.9
Default Value 90.0
Occupied High Humidity
The Occupied High Humidity
set point is used to configure the humidity set point for the zone
controller if optional zone humidity control (dehumidification)
is used.
Occupied High Humidity: Units % Humidity
Range 0.0 to 100.0
Default Value 60.0
Unoccupied High Humidity
The unoccupied high humidi-
ty set point is used to configure the unoccupied humidity set
point for the zone controller if optional zone humidity control
(dehumidification) is used.
Unoccupied
High Humidity: Units % humidity
Range 0 to 100
Default Value 100
DESCRIPTION DEFAULT POINT NAME
Manual Override Hours
0OVRD
Period 1: Day of Week
11111111 DOW1
Period 1: Occupied From
00:00 OCC1
Period 1: Occupied To
24:00 UNOCC1
Period 2: Day of Week
00000000 DOW2
Period 2: Occupied From
00:00 OCC2
Period 2: Occupied To
24:00 UNOCC2
Period 3: Day of Week
00000000 DOW3
Period 3: Occupied From
00:00 OCC3
Period 3: Occupied To
24:00 UNOCC3
Period 4: Day of Week
00000000 DOW4
Period 4: Occupied From
00:00 OCC4
Period 4: Occupied To
24:00 UNOCC4
Period 5: Day of Week
00000000 DOW5
Period 5: Occupied From
00:00 OCC5
Period 5: Occupied To
24:00 UNOCC5
Period 6: Day of Week
00000000 DOW6
Period 6: Occupied From
00:00 OCC6
Period 6: Occupied To
24:00 UNOCC6
Period 7: Day of Week
00000000 DOW7
Period 7: Occupied From
00:00 OCC7
Period 7: Occupied To
24:00 UNOCC7
Period 8: Day of Week
00000000 DOW8
Period 8: Occupied From
00:00 OCC8
Period 8: Occupied To
24:00 UNOCC8
1001