Burnham V7 SERIES Boiler User Manual


 
3
TABLE OF CONTENTS
I. General Information ............................. 3
II. Knockdown Boiler Assembly ............... 7
III. Installation Instructions...................... 12
IV. Operating Instructions........................ 21
V. Boiler Cleaning .................................. 29
VI. Repair Parts ........................................ 31
Burner Specifications ......................... 46
SECTION I: GENERAL INFORMATION
Figure 1A: V72 thru V79 Water Boiler Without Tankless Heater (WB)
TABLE 1: DIMENSIONAL DATA (SEE FIGURES 1A THRU 1E)
IMPORTANT
Before startin
g
to install this oil boiler, read these instructions carefull
y
. Kee
p
instructions in le
g
ible condition and
p
osted near oil boiler for reference b
y
owner and service technician.
Boiler
Model
No.
Dimensions
Minimum
Chimney Size
Water Content -
Gallons
Heat Transfer
Surface Area -
Sq. Ft.
Approximate
Shippin
g
Wei
g
ht
(LB.)
"A" "B" "C"
Steam
Boiler
Water
Boiler
Steam Boiler
V72 11-3/8" 6-3/8" 5" 8" x 8" x 15' ---- 10.6 ---- 381
V713 16" 8-3/4" 6" 8" x 8" x 15' ---- 13.5 ---- 524
V73 15-3/8" 8-3/8" 6" 8" x 8" x 15' 10.8 13.2 13.8 478
V714 20" 10-3/4" 6" 8" x 8" x 15' ---- 15.9 ---- 580
V74 19-3/8" 10-3/8" 6" 8" x 8" x 15' 13.5 15.9 19.7 575
V75 23-3/8" 12-3/8" 7" 8" x 8" x 15' 16.1 18.5 25.6 674
V76 27-3/8" 14-3/8" 7" 8" x 8" x 15' 18.6 21 31.4 773
V77 31-3/8" 16-3/8" 8" 8" x 12" x 15' 21.2 23.6 37.3 872
V78 35-3/8" 18-3/8" 8" 8" x 12" x 15' 23.8 26.2 43.1 971
V79 39-3/8" 20-3/8" 8" 8" x 12" x 15' 26.4 28.8 49.0 1070
NOTE: 1. Maximum Working Pressure 15 PSI (Steam) and 30 PSI (Water)
2. The V72, V713 and V714 Boilers are available as packaged water boilers only