Burnham 81433101R16-1/10 Boiler User Manual


 
30
6. Inspect the transformer cables and connectors.
7. Remove and clean the cad cell.
8. Clean the blower wheel and the air control of any
lint.
9. Check all wiring for secure connections or insulation
breaks.
10. Re-adjust the burner as detailed in Section VII:
System Start-up, Paragraph F.
E. Controls. Test Controls for proper operation as
detailed in Section VII: System Start-up, Paragraph G.
F. Low water cutoff (if so equipped).
1. Float Type
a. Monthly Blowoff. During the heating season, if
an external oat type low water cutoff is on the
boiler, the blow off valve should be opened once
a month (use greater frequency where conditions
warrant), to ush out the sediment chamber so
the device will be free to function properly.
b. Annual Service. Float type low water cutoffs
should be dismantled annually by qualied
personnel, to the extent necessary to insure
freedom from obstructions and proper
functioning of the working parts. Inspect
connecting lines to boiler for accumulation of
mud, scale, etc., and clean as required. Examine
all visible wiring for brittle or worn insulation
and make sure electrical contacts are clean
and that they function properly. Give special
attention to solder joints on bellows and oat
when this type of control is used. Check oat
for evidence of collapse and check mercury bulb
(where applicable) for mercury separation or
discoloration.
2. Probe Type (Annual Service). Probe type LWCO
should be removed once a year, examined and
cleaned of any dirt accumulations to assure proper
operations. Do not attempt to repair mechanisms
in the eld. Complete replacement mechanisms,
including necessary gaskets and installation
instructions, are available from the manufacturer.