Table 4 — Electrical Data
LEGEND
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR breaker.
The Canadian units may be fuse or circuit breaker.
2.
Unbalanced
3-Phase Supply Voltage
Never operate a motor where a phase imbalance
in supply voltage is
greater than 2%.
Use the following formula to determine the percent
of voltage imbalance.
% of Voltage Imbalance =
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance:
This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.
IMPORTANT:
If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
3. The 575-v units are CSA only.
4. The 380-v units are
not
UL or CSA listed.
UNIT
NOMINAL VOLTAGE
(V-Ph-Hz)
VOLTAGE RANGE COMPRESSOR OFM POWER SUPPLY
Min Max RLA LRA FLA MCA MOCP
569C072
208/230-3-60 187 254 21.8 158 1.9 30.1 40
460-3-60 414 508 10.0 79 1.0 13.5 20
575-3-60 518 632 9.0 65 1.9 14.1 20
569C090
208/230-3-60 187 254 28.8 195 3.8 39.8 50
460-3-60 414 508 14.7 95 1.9 20.3 25
575-3-60 518 632 10.8 80 1.9 15.4 20
569C120
208/230-3-60 187 254 37.8 239 3.1 51.1 70
460-3-60 414 508 17.2 125 1.4 23.4 30
575-3-60 518 632 14.3 90 1.4 19.8 25
576B090
208/230-3-60 187 254 31.5 160 3.1 42.5 50
380-3-60 342 418 19.0 75 2.2 26.0 35
460-3-60 414 508 15.7 80 1.4 21.0 25
575-3-60 518 632 12.6 64 1.4 17.2 20
576B102
208/230-3-60 187 254 39.7 198 3.1 52.7 70
380-3-60 342 418 24.0 93 2.2 32.2 40
460-3-60 414 508 19.9 99 1.4 26.3 35
575-3-60 518 632 15.9 79 1.4 21.3 25
576B120
208/230-3-60 187 254 39.7 198 3.1 52.7 70
380-3-60 342 418 24.0 93 2.2 32.2 40
460-3-60 414 508 19.9 99 1.4 26.3 35
575-3-60 518 632 15.9 79 1.4 21.3 25
CSA
Canadian Standards Association
FLA
Full Load Amps
HACR
Heating, Air Conditioning and Refrigeration
LRA
Locked Rotor Amps
MCA
Minimum Circuit Amps
MOCP
Maximum Overcurrent Protection
NEC
National Electrical Code
OFM
Outdoor (Condenser) Fan Motor
RLA
Rated Load Amps
UL
Underwriters’ Laboratories
100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
452 + 464 + 455
3
=
1371
3
= 457
% Voltage Imbalance = 100 x
7
457
= 1.53%