Bryant 575A Heat Pump User Manual


 
Table 4 Electrical Data
UNIT
575A
NOMINAL VOLTAGE
(V-Ph-Hz)
VOLTAGE RANGE COMPRESSOR OFM POWER SUPPLY MINIMUM DISCONNECT
Min Max RLA LRA FLA MCA
MAX FUSE OR
HACR BRKR AMPS
FLA LRA
090
208/230-3-60 187 254 31.5 160 3.1 42.5 50 45 177
460-3-60 414 508 15.7 80 1.4 21.0 25 25 89
LEGEND
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
NEC National Electrical Code
OFM Outdoor Fan Motor
RLA Rated Load Amps
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent
voltage imbalance.
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
(AB) 457 Ϫ 452=5v
(BC) 464 Ϫ 457=7v
(AC) 457 Ϫ 455=2v
Maximum deviation is 7 v.
Determine percent voltage imbalance
7
% Voltage Imbalance = 100
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
Table 5 — Accessory Electric Heater Data
UNIT
524A-H
NOMINAL kW V-PH-HZ
HEATER
PART NO.
HEATER
AMPS
MCA* MOCP*
090
5
240-3-60 CAELHEAT001A00 12.0 25.6 30
480-3-60 CAELHEAT002A00 6.0 12.3 15
10
240-3-60 CAELHEAT004A00 24.1 40.7 50
480-3-60 CAELHEAT005A00 12.0 19.8 25
15
240-3-60 CAELHEAT007A00 36.0 55.7 80
480-3-60 CAELHEAT008A00 18.0 27.4 40
25
240-3-60 CAELHEAT010A00 60.1 85.8 125
480-3-60 CAELHEAT011A00 30.1 42.4 60
35
240-3-60 CAELHEAT013A00 84.0 115.8 175
480-3-60 CAELHEAT014A00 42.1 57.4 80
LEGEND
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection (Amps)
*Sizes shown are for single-point connection of electric heat accessory
and air handler.
NOTES:
1. MCA and MOCP values apply to both standard and alternate factory-
supplied motors.
2. Electrical resistance heaters are rated at 240 v or 480 v. To deter-
mine heater capacity (kW) at unit nameplate voltage, multiply 240-v
or 480-v capacity by multipliers found in table below.
HEATER RATING
VOLTAGE
ACTUAL SITE VOLTAGE
200 208 230 240 400 440 460 480
240 .694 .751 .918 1
480 .694 .840 .918 1
NOTE: The following equation converts kW of heat energy to Btuh:
kW x 3,412 = Btuh.
—7—