Bryant 558J Fan User Manual


 
38
Table 34 MCA/MOCP DETERMINATION W/ PWRD C.O.
UNIT
V --- PH --- HZ
IFM
TYPE
ELECTRIC HEATER NO C.O. or UNPWRD C.O.
kW FLA
NO P.E. w/ P.E. (pwrd fr/unit)
MCA MOCP
DISC. SIZE
MCA MOCP
DISC. SIZE
FLA LRA FLA LRA
558J*06
208/230---1---60
STD
--- --- 39.2 60 37 150 41.1 60 40 152
4.9/6.5 23.5/27.1 39.2/40.0 60/60 37/37 150/150 41.1/42.4 60/60 40/40 152/152
6.5/8.7 31.4/36.3 45.4/51.5 60/60 42/47 150/150 47.8/53.9 60/60 44/50 152/152
9.8/13.0 46.9/54.2 64.8/73.9 70/80 60/68 150/150 67.1/76.3 70/ 80 62/70 152/152
13.1/17.4 62.8/72.5 84.6/96.8 90/100 78/89 150/150 87.0/99.1 90/100 80/91 152/152
15.8/21.0 75.8/87.5 100.9/115.5 110/125 93/106 150/150 103.3/117.9 110/125 95/108 152/152
MED
--- --- 41.3 60 40 175 43.2 60 42 177
4.9/6.5 23.5/27.1 41.3/42.6 60/60 40/40 175/175 43.2/45.0 60/60 42/42 177/177
6.5/8.7 31.4/36.3 48.0/54.1 60/60 44/50 175/175 50.4/56.5 60/60 46/52 177/177
9.8/13.0 46.9/54.2 67.4/76.5 70/80 62/70 175/175 69.8/78.9 70/ 80 64/73 177/177
13.1/17.4 62.8/72.5 87.3/99.4 90/100 80/91 175/175 89.6/101.8 90/110 82/94 177/177
15.8/21.0 75.8/87.5 103.5/118.1 110/125 95/109 175/175 105.9/120.5 110/125 97/111 177/177
208/230---3---60
STD
--- --- 25.9 30 25 126 27.8 40 27 128
4.9/6.5 13.6/15.6 25.9/25.9 30/30 25/25 126/126 27.8/28.0 40/40 27/27 128/128
7.9/10.5 21.9/25.3 33.5/37.8 40/40 31/35 126/126 35.9/40.1 40/ 45 33/37 128/128
12.0/16.0 33.4/38.5 47.9/54.3 50/60 44/50 126/126 50.3/56.6 60/60 46/52 128/128
15.8/21.0 43.8/50.5 60.9/69.3 70/70 56/64 126/126 63.3/71.6 70/80 58/66 128/128
19.9/26.5 55.2/63.8 75.1/85.9 80/90 69/79 126/126 77.5/88.3 80/90 71/81 128/128
MED
--- --- 26.2 40 26 144 28.1 40 28 146
4.9/6.5 13.6/15.6 26.2/26.2 40/40 26/26 144/144 28.1/28.4 40/40 28/28 146/146
7.9/10.5 21.9/25.3 33.9/38.1 40/40 31/35 144/144 36.3/40.5 40/ 45 33/37 146/146
12.0/16.0 33.4/38.5 48.3/54.6 50/60 44/50 144/144 50.6/57.0 60/60 47/52 146/146
15.8/21.0 43.8/50.5 61.3/69.6 70/70 56/64 144/144 63.6/72.0 70/80 59/66 146/146
19.9/26.5 55.2/63.8 75.5/86.3 80/90 69/79 144/144 77.9/88.6 80/90 72/82 146/146
HIGH
--- --- 28.5 40 28 170 30.4 45 30 172
4.9/6.5 13.6/15.6 28.5/28.9 40/40 28/28 170/170 30.4/31.3 45/45 30/30 172/172
7.9/10.5 21.9/25.3 36.8/41.0 40/45 34/38 170/170 39.1/43.4 45/ 45 36/40 172/172
12.0/16.0 33.4/38.5 51.1/57.5 60/60 47/53 170/170 53.5/59.9 60/60 49/55 172/172
15.8/21.0 43.8/50.5 64.1/72.5 70/80 59/67 170/170 66.5/74.9 70/80 61/69 172/172
19.9/26.5 55.2/63.8 78.4/89.1 80/90 72/82 170/170 80.8/91.5 90/100 74/84 172/172
460--- 3 --- 60
STD
--- --- 12.5 20 12 60 13.5 20 13 61
6.0 7.2 12.5 20 12 60 13.5 20 13 61
11.5 13.8 19.9 20 18 60 21.1 25 19 61
14.0 16.8 23.6 25 22 60 24.9 25 23 61
23.0 27.7 37.3 40 34 60 38.5 40 35 61
25.5 30.7 41.0 45 38 60 42.3 45 39 61
MED
--- --- 13.0 20 13 69 14.0 20 14 70
6.0 7.2 13.0 20 13 69 14.0 20 14 70
11.5 13.8 20.5 25 19 69 21.8 25 20 70
14.0 16.8 24.3 25 22 69 25.5 30 23 70
23.0 27.7 37.9 40 35 69 39.1 40 36 70
25.5 30.7 41.6 45 38 69 42.9 45 39 70
HIGH
--- --- 13.8 20 14 82 14.8 20 15 83
6.0 7.2 13.8 20 14 82 14.8 20 15 83
11.5 13.8 21.5 25 20 82 22.8 25 21 83
14.0 16.8 25.3 30 23 82 26.5 30 24 83
23.0 27.7 38.9 40 36 82 40.1 45 37 83
25.5 30.7 42.6 45 39 82 43.9 45 40 83
575--- 3 --- 60
STD --- --- 9.8 15 10 46 11.7 15 12 48
MED --- --- 10.7 15 11 63 12.6 15 13 65
HIGH --- --- 10.7 15 11 63 12.6 15 13 65
LEGEND:
CO --- Convenient outlet
DISC --- Disconnect
FLA --- Full load amps
IFM --- Indoor fan motor
LRA --- Locked rotor amps
MCA --- Mi nimum circuitamps
MOCP --- Maximum over current protection
PE --- Power exhaust
UNPWRD CO --- Unpowered convenientoutlet
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion l oa d equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage
is greater than 2%. Use the following formula to determine the
percentage of voltage imbalance.
%VoltageImbalance =100x
max voltage de viationfromaveragevoltage
averagevoltage
Example: Supply voltage is 230-3-60
AB = 224 v
BC = 231 v
AC = 226 v
AverageVoltage =
(224+231 +226)
=
681
3
3
= 227
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v Maximum deviation is 4 v.
(BC) 231 – 227 = 4v Determine percent of voltage imbalance.
%VoltageImbalance =100 x
4
227
=1.76%
This amount of phase imbalance issatisfactory as it is below the maximum
allowable2%.
IMPORTANT: If the supply voltage phaseimbalance is more than 2%, con-
tact your local electric utility company immediately.
558J