Bryant 558J Fan User Manual


 
28
FAN PERFORMANCE (cont.)
Table 19 558J*05 3 PHASE 4 TON HORIZONTAL SUPPLY
CFM
AVAILABLEEXTERNALSTATICPRESSURE(IN.WG)
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
1200 643 0.23 762 0.35 860 0.46 944 0.58 1020 0.71
1300 674 0.28 791 0.40 887 0.52 970 0.65 1045 0.78
1400 706 0.33 820 0.45 914 0.59 997 0.72 1071 0.86
1500 738 0.38 849 0.52 942 0.66 1024 0.80 1097 0.95
1600 771 0.44
879
0.59 971 0.74 1051 0.89 1124 1.04
1700 804 0.51 910 0.66 1000 0.82 1079 0.98 1151 1.14
1800 837 0.59 941 0.75 1029 0.91 1107 1.08 1178 1.25
1900 871 0.67 972 0.84 1059 1.02 1136 1.19 1206 1.37
2000 906 0.76 1004 0.94 1089 1.12 1165 1.31 1234 1.49
CFM
AVAILABLEEXTERNALSTATICPRESSURE(IN.WG)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option High Static Option
1200 1089 0.84 1153 0.98 1212 1.12 1269 1.26 1322 1.41
1300 1114 0.92 1177 1.06 1236 1.21 1292 1.36 1346 1.52
1400 1139 1.01 1202 1.15 1261 1.31 1316 1.47 1369 1.63
1500 1164 1.10 1227 1.25 1285 1.41 1341 1.58 1394 1.75
1600 1190 1.20 1252 1.36 1311 1.53 1366 1.70 1418 1.87
1700 1217 1.31 1278 1.48 1336 1.65 1391 1.83 1443 2.01
1800 1244 1.42 1305 1.60 1362 1.78 1416 1.97 1468 2.15
1900 1271 1.55 1331 1.73 1388 1.92 1442 2.11 1494 2.31
2000 1298 1.68 1358 1.87 1415 2.07 1468 2.27 --- ---
NOTE: For more information, see General Fan Performance Notes on page 23.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied fan pul ley (part no. KR11AZ506), motor pulley (part no. KR11HY181 and belt (part n o. KR30AE041).
Table 20 558J*05 3 PHASE 4 TON VERTICAL SUPPLY
CFM
AVAILABLEEXTERNALSTATICPRESSURE(IN.WG)
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Static Option Medium Static Option
1200 666 0.25 778 0.36 873 0.48 956 0.60 1031 0.72
1300 701 0.30 809 0.42 902 0.54 983 0.67 1057 0.80
1400 737 0.36
842
0.48 932 0.61 1012 0.75 1085 0.89
1500 774 0.42 875 0.55 962 0.69 1041 0.83 1112 0.98
1600 811 0.49 909 0.63 994 0.78 1071 0.93 1141 1.08
1700 849 0.57 943 0.72 1026 0.87 1101 1.03 1170 1.19
1800 887 0.65 978 0.81 1059 0.98 1133 1.14 1200 1.31
1900 926 0.75 1014 0.92 1092 1.09 1164 1.26 1231 1.44
2000 965 0.86 1050 1.03 1127 1.21 1197 1.39 1262 1.58
CFM
AVAILABLEEXTERNALSTATICPRESSURE(IN.WG)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option High Static Option
1200 1100 0.85 1165 0.98 1225 1.12 1282 1.26 1337 1.40
1300 1126 0.94 1189 1.07 1249 1.22 1306 1.36 1360 1.51
1400 1152 1.03 1215 1.17 1274 1.32 1330 1.48 1384 1.63
1500
1179 1.13 1241 1.28 1300 1.44 1355 1.60 1408 1.76
1600 1206 1.24 1268 1.40 1326 1.56 1381 1.73 1433 1.90
1700 1235 1.36 1295 1.52 1352 1.69 1407 1.87 1459 2.04
1800 1264 1.48 1323 1.66 1380 1.84 1434 2.02 1485 2.20
1900 1293 1.62 1352 1.80 1408 1.99 1461 2.17 1512 2.37
2000 1324 1.77 1381 1.96 1436 2.15
1489 2.34 --- ---
NOTE: For more information, see General Fan Performance Notes on page 23.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied fan pul ley (part no. KR11AZ506), motor pulley (part no. KR11HY181 and belt (part n o. KR30AE041).