Table 33 MCA/MOCP DETERMINATION NO C.O. OR UNPWRD C.O.
UNIT
V --- PH --- HZ
IFM
TYPE
ELECTRIC HEATER NO C.O. or UNPWRD C.O.
kW FLA
NO P.E. w/ P.E. (pwrd fr/unit)
MCA MOCP
DISC. SIZE
MCA MOCP
DISC. SIZE
FLA LRA FLA LRA
558J*05
208/230---1---60
STD
--- --- 33.7 50 32 133 35.6 50 35 135
3.3/4.4 15.9/18.3 33.7/33.7 50/50 32/32 133/133 35.6/35.6 50/50 35/35 135/135
6.5/8.7 31.4/36.3 45.4/51.5 50/60 42/47 133/133 47.8/53.9 50/60 44/50 135/135
9.8/13.0 46.9/54.2 64.8/73.9 70/80 60/68 133/133 67.1/76.3 70/ 80 62/70 135/135
13.1/17.4 62.8/72.5 84.6/96.8 90/100 78/89 133/133 87.0/99.1 90/100 80/91 135/135
15.8/21.0 75.8/87.5 100.9/115.5 110/125 93/106 133/133 103.3/117.9 110/125 95/108 135/135
MED
--- --- 33.7 50 32 133 35.6 50 35 135
3.3/4.4 15.9/18.3 33.7/33.7 50/50 32/32 133/133 35.6/35.6 50/50 35/35 135/135
6.5/8.7 31.4/36.3 45.4/51.5 50/60 42/47 133/133 47.8/53.9 50/60 44/50 135/135
9.8/13.0 46.9/54.2 64.8/73.9 70/80 60/68 133/133 67.1/76.3 70/ 80 62/70 135/135
13.1/17.4 62.8/72.5 84.6/96.8 90/100 78/89 133/133 87.0/99.1 90/100 80/91 135/135
15.8/21.0 75.8/87.5 100.9/115.5 110/125 93/106 133/133 103.3/117.9 110/125 95/108 135/135
208/230---3---60
STD
--- --- 23.5 30 23 99 25.4 30 25 101
4.9/6.5 13.6/15.6 23.5/25.6 30/30 23/24 99/99 25.5/28.0 30/30 25/26 101/101
6.5/8.7 18.1/20.9 28.8/32.3 30/35 26/30 99/99 31.1/34.6 35/35 29/32 101/101
12.0/16.0 33.4/38.5 47.9/54.3 50/60 44/50 99/99 50.3/56.6 60/60 46/52 101/101
15.8/21.0 43.8/50.5 60.9/69.3 70/70 56/64 99/99 63.3/71.6 70/80 58/66 101/101
MED
--- --- 23.5 30 23 99 25.4 30 25 101
4.9/6.5 13.6/15.6 23.5/25.6 30/30 23/24 99/99 25.5/28.0 30/30 25/26 101/101
6.5/8.7 18.1/20.9 28.8/32.3 30/35 26/30 99/99 31.1/34.6 35/35 29/32 101/101
12.0/16.0 33.4/38.5 47.9/54.3 50/60 44/50 99/99 50.3/56.6 60/60 46/52 101/101
15.8/21.0 43.8/50.5 60.9/69.3 70/70 56/64 99/99 63.3/71.6 70/80 58/66 101/101
HIGH
--- --- 23.8 30 23 117 25.7 30 26 119
4.9/6.5 13.6/15.6 23.8/26.0 30/30 23/24 117/117 25.9/28.4 30/30 26/26 119/119
6.5/8.7 18.1/20.9 29.1/32.6 30/35 27/30 117/117 31.5/35.0 35/40 29/32 119/119
12.0/16.0 33.4/38.5 48.3/54.6 50/60 44/50 117/117 50.6/57.0 60/60 47/52 119/119
15.8/21.0 43.8/50.5 61.3/69.6 70/70 56/64 117/117 63.6/72.0 70/80 59/66 119/119
460--- 3 --- 60
STD
--- --- 10.7 15 10 49 11.7 15 12 50
6.0 7.2 11.6 15 11 49 12.9 15 12 50
11.5 13.8 19.9 20 18 49 21.1 25 19 50
14.0 16.8 23.6 25 22 49 24.9 25 23 50
23.0 27.7 37.3 40 34 49 38.5 40 35 50
MED
--- --- 10.7 15 10 49 11.7 15 12 50
6.0 7.2 11.6 15 11 49 12.9 15 12 50
11.5 13.8 19.9 20 18 49 21.1 25 19 50
14.0 16.8 23.6 25 22 49 24.9 25 23 50
23.0 27.7 37.3 40 34 49 38.5 40 35 50
HIGH
--- --- 11.2 15 11 58 12.2 15 12 59
6.0 7.2 12.3 15 11 58 13.5 15 12 59
11.5 13.8 20.5 25 19 58 21.8 25 20 59
14.0 16.8 24.3 25 22 58 25.5 30 23 59
23.0 27.7 37.9 40 35 58 39.1 40 36 59
575--- 3 --- 60
STD --- --- 7.3 15 7 44 9.2 15 9 46
MED --- --- 7.3 15 7 44 9.2 15 9 46
HIGH --- --- 7.4 15 7 50 9.3 15 10 52
LEGEND:
CO --- Convenient outlet
DISC --- Disconnect
FLA --- Full load amps
IFM --- Indoor fan motor
LRA --- Locked rotor amps
MCA --- Mi nimum circuitamps
MOCP --- Maximum over current protection
PE --- Power exhaust
UNPWRD CO --- Unpowered convenientoutlet
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion l oa d equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage
is greater than 2%. Use the following formula to determine the
percentage of voltage imbalance.
%VoltageImbalance =100x
max voltage de viationfromaveragevoltage
averagevoltage
Example: Supply voltage is 230-3-60
AB = 224 v
BC = 231 v
AC = 226 v
AverageVoltage =
(224+231 +226)
=
681
3
3
= 227
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v Maximum deviation is 4 v.
(BC) 231 – 227 = 4v Determine percent of voltage imbalance.
%VoltageImbalance =100 x
4
227
=1.76%
This amount of phase imbalance issatisfactory as it is below the maximum
allowable2%.
IMPORTANT: If the supply voltage phaseimbalance is more than 2%, con-
tact your local electric utility company immediately.