Bryant 558D Heating System User Manual


 
Table 2 Electrical Data (Cont)
UNIT
558D
NOMINAL
V-PH-Hz
IFM
TYPE
VOLTAGE
RANGE
COMPR
(each)
OFM IFM ELECTRIC HEAT* POWER SUPPLY
DISCONNECT
SIZE**
Min Max RLA LRA FLA FLA Nominal kW FLA MCA MOCP† FLA LRA
060
(5 Ton)
208/230-1-60
Std
187 254 28.8 147 1.4
5.9
43.3/ 43.3 60/ 60 42/ 42 159/159
4.9/ 6.5 23.5/27.1 43.3/ 43.3 60/ 60 42/ 42 159/159
6.5/ 8.7 31.4/36.3 46.6/ 52.7 60/ 60 43/ 49 159/159
9.8/13.0 46.9/54.2 66.0/ 75.1 70/ 80†† 61/ 69 159/159
13.0/17.4 62.8/72.5 85.9/ 98.0 90/100†† 79/ 90 159/159
15.8/21.0 75.8/87.5 102.2/116.8 110/125†† 94/107 159/159
Alt 8.8
46.2/ 46.2 60/ 60 45/ 45 162/162
4.9/ 6.5 23.5/27.1 46.2/ 46.2 60/ 60 45/ 45 162/162
6.5/ 8.7 31.4/36.3 49.9/ 55.9 60/ 60 46/ 52 162/162
9.8/13.0 46.9/54.2 69.3/ 78.3 70/ 80†† 64/ 72 162/162
13.0/17.4 62.8/72.5 89.2/101.3 90/110†† 82/ 93 162/162
15.8/21.0 75.8/87.5 105.5/120.0 110/125†† 97/110 162/162
208/230-3-60
Std
187 254 16.3 114 1.4
5.9
27.7/ 27.7 35/ 35 27/ 27 126/126
4.9/ 6.5 13.6/15.6 27.7/ 27.7 35/ 35 27/ 27 126/126
7.9/10.5 21.9/25.3 34.7/ 38.9 40/ 40 32/ 36 126/126
12.0/16.0 33.4/38.5 49.1/ 55.5 50/ 60 46/ 51 126/126
15.8/21.0 43.8/50.5 62.1/ 70.5 70/ 80†† 57/ 65 126/126
19.9/26.5 55.2/63.8 76.4/ 87.1 80/ 90†† 70/ 80 126/126
Alt 5.8
26.8/ 26.8 40/ 40 27/ 27 125/125
4.9/ 6.5 13.6/15.6 26.8/ 26.8 40/ 40 27/ 27 125/125
7.9/10.5 21.9/25.3 35.3/ 39.5 45/ 45 32/ 36 125/125
12.0/16.0 33.4/38.5 49.6/ 56.0 60/ 60 45/ 51 125/125
15.8/21.0 43.8/50.5 62.6/ 71.1 70/ 80†† 57/ 65 125/125
19.9/26.5 55.2/63.8 77.0/ 87.6 80/100†† 70/ 80 125/125
460-3-60
Std
414 508 7.4 64 0.8
3.2
13.3 20 13 69
6.0 7.2 13.3 20 13 69
11.5 13.8 21.3 25 20 69
14.0 16.8 25.0 30 23 69
23.0 27.7 38.6 40 36 69
25.5 30.1 41.6 45 38 69
Alt 2.6
12.7 20 12 70
6.0 7.2 12.7 20 12 70
11.5 13.8 21.0 25 19 70
14.0 16.8 24.8 30 22 70
23.0 27.7 38.3 45 35 70
25.0 30.1 41.3 45 38 70
575-3-60
Std
518 632 6.2 52 0.8
3.2 11.8 15 12 57
Alt 2.6 11.2 15 12 59
072
(6 Ton)
208/230-3-60 Std 187 254 23.6 146.0 1.4 5.2
36.1/ 36.1 45/ 45 35/ 35 191/191
4.9/ 6.5 13.6/15.6 36.1/ 36.1 45/ 45 35/ 35 191/191
7.9/10.5 21.9/25.3 36.1/ 38.1 45/ 45 35/ 35 191/191
12.0/16.0 33.4/38.4 48.2/ 54.6 50/ 60 44/ 50 191/191
15.8/21.0 43.8/50.5 61.2/ 69.6 70/ 70†† 56/ 64 191/191
19.9/26.5 55.2/63.8 75.6/ 86.2 80/ 90†† 70/ 79 191/191
460-3-60 Std 414 508 10.6 73.0 0.8 2.6
16.7 20 16 90
6.0 7.2 16.7 20 16 90
11.5 13.8 20.5 25 19 90
14.0 16.8 24.3 25 22 90
23.0 27.8 37.8 40 35 90
25.5 30.7 41.6 45 38 90
575-3-60 Std 518 632 8.5 58.4 0.8 2.6 13.3 20 14 75
IMPORTANT: Optional, alternate evaporator-fan motor and drive are not available for
558D072 units. Contact your local representative for more information about field-
installed motors.
LEGEND
COMPR Compressor
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
IFM Indoor (Evaporator) Fan Motor
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
NEC National Electrical Code
OFM Outdoor (Condenser) Fan Motor
RLA Rated Load Amps
*Available for field-installed accessory heaters only. Heater capacity (kW) is based on
heater voltage of 208 v, 240 v or 480 v. If power distribution voltage to unit varies from
rated heater voltage, heater kW will vary accordingly.
†Fuse or HACR circuit breaker.
**Used to determine minimum disconnect per NEC.
††Fusing single-point box provides the required branch circuit protection.
Ampacities are based on 460 v. MCA and MOCP are based on 575 v.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equip-
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than
2%.
Use the following formula to determine the percent of voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
NOTE: The 575-v units are Canada only.
Determine maximum deviation from average voltage.
(AB) 457 - 452=5v
(BC) 464 - 457=7v
(AC) 457 - 455=2v
Maximum deviation is 7 v.
Determine percent voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allow-
able 2%.
IMPORTANT: If the supplyvoltage phase imbalance is more than2%, contact your
local electric utility company immediately.
—11—