ELECTRICAL DATA
UN IT SI ZE ---
SERIES
V/PH
OPER VOLTS* COMPR FAN
MCA
MIN
WIRE
SIZE†
MIN
WIRE
SIZE†
MAX
LENGTH
ft (m)‡
MAX
LENGTH
ft (m)‡
MAX
FUSE**
or CKT
BRK
AMPS
MAX MIN LRA RLA FLA 60° C 75° C 60° C 75° C
018---C
208/230/1 253 197
48.0 9.0 0.7 11.9 14 14 66 (20.1) 62 (18.9) 20
024---B 58.3 12.8 0.7 16.7 14 14 47 (14.3) 45 (13.7) 25
030---C 77.0 16.0 0.8 20.8 12 12 60 (18.3) 57 (17.4) 30
036---C 79.0 17.1 0.9 22.3 12 12 56 (17.1) 53 (16.2) 35
042---B 109.0 19.9 1.2 26.0 10 10 77 (23.5) 73 (22.3) 40
048---B 117.0 27.3 1.2 35.4 8 8 88 (26.8) 84 (25.6) 50
060---B 134.0 26.3 1.2 34.1 8 8 91 (27.7) 87 (26.5) 50
030---B
208/230/3 253 197
71.0 10.0 0.8 13.3 14 14 64 (19.5) 61 (18.6) 20
036---C 73.0 11.5 0.9 15.3 12 12 94 (28.7) 90 (27.4) 25
042---B 88.0 13.5 1.2 18.0 10 10 128 (39.0) 122 (37.2) 30
048---B 83.1 17.2 1.2 22.7 8 10 158 (48.2) 97 (29.6) 35
060---B 110.0 17.0 1.2 22.5 8 10 160 (48.8) 98 (29.9) 35
036---C
460/3 506 414
38.0 5.2 0.5 7.0 14 14 260 (79.2) 247 (75.3) 15
042---B 46.0 7.1 0.53 9.3 14 14 196 (59.7) 186 (56.7) 15
048---B 41.0 7.5 0.6 10.0 14 14 182 (55.5) 173 (52.7) 15
060---B 52.0 7.8 0.6 10.3 14 14 177 (54.0) 168 (51.2) 15
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30_C, consult table 310---16 of the NEC (ANSI/NFPA 70). The ampacity of non---metallic---sheathed cable (NM),
trade name ROMEX, shall be that of 60_C conditions, per the NEC (ANSI/NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or 75_C insula
tion, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA70).
} Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time --- Delay fuse.
FLA --- Full Load Amps
LRA --- Locked Rotor Amps
MC A --- Minimum Circuit Amps
RLA --- RatedLoadAmps
NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2001 requirements of ASHRAE Standards 90.1
A--WEIGHTED SOUND POWER
UNIT SIZE---SERIES (VOLTAGE)
STANDARD
RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA , without tone adjustment)
125 250 500 1000 2000 4000 8000
018---C (N) 73 58.5 62.5 67.0 67.5 65.5 62.5 53.5
024---B (N) 72 54.5 63.0 66.5 66.0 64.0 60.5 51.5
030---C (N) 73 57.0 63.5 68.0 69.0 65.0 61.0 52.5
030---B (P) 72 53.0 60.5 66.0 67.5 64.5 61.5 53.0
036---C (N) 70 54.5 62.0 63.5 64.5 63.0 60.0 51.5
036---C (P, E) 73 57.0 63.5 68.0 69.0 65.0 61.0 52.5
042---B (N, P, E) 73 55.0 60.0 64.0 67.5 61.5 60.0 55.0
048---B (N, P, E) 74 57.5 64.5 67.5 69.5 66.5 61.0 53.0
060---B (N, P, E) 74 53.5 63.0 67.5 70.0 63.5 60.0 55.5
NOTE: Tested in accordance with ARI Standard 270---95 (not listed in ARI).
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE---SERIES (VOLTAGE) REQUIRED SUBCOOLING _F(_C)
018---C (N) 10 (5.6)
024---B (N) 12 (6.7)
030---C (N), B (P) 12 (6.7)
036---C (N, P,E) 10 (5.6)
042---B (N, P, E) 11 (6.1)
048---B (N, P, E) 11 (6.1)
060---B (N, P, E) 12 (6.7)
223A