Accessory Description and Usage (Listed Alphabetically) -- CONTINUED
5. Evaporator Freeze Thermostat
An SPST temperature--actuated switch that stops unit operation
when evaporator reaches freeze--up conditions.
Usage Guideline:
Required when low ambient kit has been added.
6. Isolation Relay
An SPDT relay which switches the low--ambient controller out of
the outdoor fan motor circuit when the heat pump switches to
heating mode.
Usage Guideline:
Required in all heat pumps where low ambient kit has
been added.
7. Liquid--Line Solenoid Valve (LLS)
An electrically operated shutoff valve which stops and starts
refrigerant liquid flow in response to compressor operation. It is
to be installed at the outdoor unit to control refrigerant off cycle
migration in the heating mode.
Usage Guideline:
An LLS is required in all long line heat pump
applications to control refrigerant off cycle migration in
the heating mode. See Long Line Guideline.
8. Low--Ambient Pressure Switch Kit
A long life pressure switch which is mounted to outdoor unit
service valve. It is designed to cycle the outdoor fan motor in
order to maintain head pressure within normal operating limits.
The control will maintain working head pressure at low--ambient
temperatures down to 0_F (--17.8_C)when properly installed.
Usage Guideline:
A Low--Ambient Pressure Switch or MotorMasterr
Low--Ambient Controller must be used when cooling
operation is used at outdoor temperatures below 55_F
(12.8_C).
9. MotorMasterr Low--Ambient Controller
A fan--speed control device activated by a temperature sensor,
designed to control condenser fan motor speed in response to the
saturated, condensing temperature during operation in cooling
mode only. For outdoor temperatures down to --20_F (--28.9_C),
it maintains condensing temperature at 100_F ±10_F (37.8_C ±
6.5_C).
Usage Guideline:
A MotorMasterr Low Ambient Controller or
Low--Ambient Pressure Switch must be used when
cooling operation is used at outdoor temperatures
below 55_F (12.8_C).
Suggested for all commercial applications.
10. Outdoor Air Temperature Sensor
Designed for use with Bryant Thermostats listed in this
publication. This device enables the thermostat to display the
outdoor temperature. This device also is required to enable
special thermostat features such as auxiliary heat lock out.
Usage Guideline:
Suggested for all Bryant thermostats listed in this
publication.
11. Outdoor Thermostat
An SPDT temperature--actuated switch which turns on
supplemental electric heaters when outdoor air temperature drops
below a user--selected set point.
Usage Guideline:
Electric supplemental heat applications in non--variable
speed indoor units when electric heat staging is desired.
12. Secondary Outdoor Thermostat
An SPDT temperature--actuated switch which turns on
third--stage of supplemental electric heaters when outdoor air
temperature drops below the second--stage set point.
Usage Guideline:
Outdoor thermostat applications where electric heater is
capable of three--stage operation.
13. Snow Stand
Coated wire rack which supports unit 18 in. (457.2 mm) above
mounting pad to allow for drainage from unit base.
Usage Guideline:
Suggested in the following applications:
Heat pump installations in heavy snowfall areas.
Heat pump installations in snow drift locations.
Heat pump installations in areas of prolonged
subfreezing temperatures.
All commercial installations.
14. Sound Hood
Wraparound sound reducing cover for the compressor. Reduces
the sound level by about 2 dBA.
Usage Guideline:
Suggested when unit is installed closer than 15 ft.
(4.577 m) to quiet areas, bedrooms, etc.
Suggested when unit is installed between two houses
less than 10 ft. (3.05 m) apart.
15. Thermostatic Expansion Valve (TXV) Bi--Flow
A modulating flow--control valve which meters refrigerant liquid
flow rate into the evaporator in response to the superheat of the
refrigerant gas leaving the evaporator.
Usage Guideline:
Accessory required to meet ARI rating and system
reliability, where indoor not equipped.
Required in all heat pump applications designed with
Puron refrigerant.
16. Time--Delay Relay
An SPST delay relay which briefly continues operation of indoor
blower motor to provide additional cooling after the compressor
cycles off.
Note: Most indoor unit controls include this feature. For those
that do not, use the guideline below.
Usage Guideline:
Accessory required to meet ARI rating, where indoor
not equipped.