SERVICE PROCEDURE RG-VI
Gas Control
Testing, Disassembly & Replacement (Honeywell)
The Bradford White
DEFENDER
Safety System
®
GAS CONTROL DISASSEMBLY/REASSEMBLY
Step 1. Rotate knob of the Gas Control to the “OFF” position.
Step 2. Turn off gas supply to water heater.
Step 3. Disconnect gas supply line from Gas Control.
Step 4. Disconnect piezo igniter wire.
Step 5. Remove inner door assembly following SERVICE PROCEDURE RG-I, steps 1 through 3c.
Step 6. Remove Gas Control cover screw.
Rotate knob counter-clockwise
to the “OFF” posistion.
Step 7. Depress both tabs on the top of the Gas Control cover and pull to remove.
Gas Control
cover screw
CAUTION
Use caution not to bend or damage valve body pins
when removing or installing Gas Control cover.
Valve body pins