Boiler should be located within 15 feet (4.6m) of the
supply and return headers. The pump is sized for 30 feet
(9.1m) of piping.
If the appliance must be installed with longer piping
runs, then larger diameter tubing shall be used. Consult
the factory for assistance.
1.8 Locating Appliance for Correct
Horizontal Vent/Ducted Air Distance
from Outside Wall
The forced draft combustion air blower/blowers in
the appliance has/have sufficient power to pull air and
vent properly when the following guidelines for
horizontal air and vent are followed (see Table 2).
Figure 1. Dimensional Data (standard units).
Air Vent Shipping Weight
1
Conn. Conn.
Size A B C D E W V lbs kg
500 33¾ 85 16¾ 43 17 10 25 8 20 6 15 8 20 425 193
750 45¾ 116 22¾ 53 17 10 25 24 6 15 10 25 505 229
1000 57¾ 147 28¾ 73 17 10 25 24 8 20 10 25 615 279
1250 68¼ 173 34 87 10¼ 26 10 25 9 23 8 20 12 30 675 306
1500 78¾ 200 39½ 100 10¼ 26 10 25 9 23 8 20 12 30 760 345
1750 89¼ 227 44¾ 113 10¼ 26 10 25 9 23 8 20 12 30 825 375
2000 99¾ 253 49¾ 127 10¼ 26 10 25 9 23 12 30 14 36 955 434
NOTES: 1. Add 55 lbs (25kg) for pump-mounted units.
Dimensions in inches cm.