number to reduce CO
2
by 2 percentage points
at a zero smoke level. (Increase O
2
by 3
percentage points at a zero smoke level.)
Example: Reduce CO
2
from 13.5% to 11.5%,
with zero smoke (or increase O
2
from 2.5% to
5.5%).
A margin of reserve air has been added to
accommodate variable conditions.
Check the breech draft pressure against the
appliance manufacturer’s recommended setting
(typically + 0.1” W.C.).
If the breech pressure is higher or lower than
recommended level, adjust the appliance breech
damper to achieve the speci ed setting. Recheck
the smoke and CO
2
(or O
2
) levels. Adjust burner air
if necessary.
Once all settings are complete and satisfactory,
proceed to ‘Set Low- re Air’ Section.
Set Low- re Air
Move the low- re hold switch from the high re
position to the low re hold position.
The damper will return to the low- re air
setting.
Check the smoke and CO
2
(O
2
) levels.
Pull a smoke sample from the ue.
The sample should be clean (zero smoke level).
Check the CO
2
(O
2
) level:
CO
2
should be at 11 to 12% (O
2
at 5.9 to 4.5%).
If the CO
2
is less than 11% (O
2
more than
5.9%), decrease the air and check the smoke
level.
Operate the burner from low re to high re and
back to verify operation.
Turn the burner off. Wait one or two minutes (for
chamber to clear) and then turn on again to verify
starting characteristics.
Perform limit circuit performance test speci ed
by appliance manufacturer to verify operation of
burner/appliance combination.
c.
7.
8.
9.
1.
a.
2.
a.
b.
c.
d.
e.
3.
4.
5.
If the burner motor does not start, reset the motor
overload switch (if so equipped) and press the reset
switch of the burner primary control.
Vent the fuel unit as soon as the burner motor starts
rotating. To vent —
Attach a clear plastic tube to the air bleed valve
(Figure 9 or 10 as applies, item p).
Place the end of the tube in a container to catch
the oil. Then loosen the fuel unit air vent valve.
Tighten the air vent valve after all air has been
purged.
IF burner stops during venting
The burner primary control will lockout if
ame is not established within its time limit.
This is typically 15 seconds for 7505 primary
controls, but may be less for other ame
supervisory controls.
The burner may lockout several times during
the period needed to purge all the air. To
extend air venting time, press the red reset
button for 1/2 second during the prepurge
cycle to continue purging with 7505 controls.
IF burner stops after ame established
Additional venting is probably required.
Repeat the air venting procedure.
Once ame is steady, proceed to the ‘Set High- re
Air’ Section air.
Set High- re Air
Allow the burner to run at low re until the
appliance has warmed suf ciently.
Visually check the ame. The ame should not be
dark orange or smoky. If the ame appears to be
smoking, increase the amount of air by readjusting
the damper indicator to a higher number.
Once the appliance has warmed, the high- re
setting can be checked and adjusted.
Locate the approximate air adjusting plate setting
for high re in Table 4.
Place the low- re hold switch in the high- re
position. The damper motor will begin to rotate
after four seconds.
Use combustion test instruments to adjust the
burner.
Adjust the air by moving the red cam to a lower
number until a trace of smoke is achieved with
CO
2
level as high as possible (lowest possible
O
2
).
Example: 13.5% CO
2
(2.5% O
2
) with a trace of
smoke.
Increase the air by increasing the red cam
6.
7.
-
-
-
8.
1.
2.
3.
4.
5.
6.
a.
b.
Section: Prepare the Burner for Start-up