Beckett CF1000 Burner User Manual


 
Form 6104 BCF10-R06
15
Set appliance limit controls
Set the appliance limit controls in accordance with the
appliance manufacturer’s recommendations.
Prepare the fuel unit for air venting
To vent air from one-pipe oil systems, attach a clear hose to
the vent plug on the fuel unit. Provide a container to catch
the oil. Loosen the vent plug.
Vent the air as described under Start the burner.
y
y
y
Start the Burner
Starting the burner and venting air
Do not attempt to start the burner when excess oil has
accumulated in the appliance, the appliance is full of
vapor, or when the combustion chamber is very hot.
Do not attempt to re-establish ame with the burner
running if the ame becomes extinguished during start-
up, venting, or adjustment.
Vapor-Filled Appliance: Allow the unit to cool off and
all vapors to dissipate before attempting another start.
Oil-Flooded Appliance: Shut off the electrical power
and the oil supply to the burner and then clear all ac-
cumulated oil before continuing.
If the condition still appears unsafe, contact the Fire De-
partment. Carefully follow their directions.
Keep a re extinguisher nearby and ready for use.
y
y
y
y
y
y
Failure to follow these instructions
could lead to equipment malfunction
and result in heavy smoke emission,
soot-up, hot gas puff-back, re and
asphyxiation hazards.
Explosion and Fire
Hazard
Do not allow oil to intermittently spray into a hot com-
bustion chamber while bleeding.
Install a gauge in the nozzle discharge port tubing or
fully open the pump bleed valve to prevent oil spray
from accumulating in the combustion chamber when
venting air from the fuel pump.
Ensure that all bubbles and froth are purged from the
oil supply system before tightening the pump air bleed
valve.
y
y
y
Failure to bleed the pump properly
could result in unstable combustion,
hot gas puff-back and heavy smoke.
Hot Gas Puff-back and
Heavy Smoke Hazard
Verify that the air adjusting plate (Figure 12, item m) has
been set to the initial air position as described on page 14
under Initial air settings.
Open the oil shut-off valves in the oil supply (and return)
line(s) to the burner.
Set the thermostat (or operating control) to call for heat.
Close the line switch to the burner. The burner motor should
start immediately.
1.
2.
3.
4.