Beckett ADC Burner User Manual


 
3
12 Vdc ADC Burner Manual
Section: Prepare Before Installing
Owner’s Responsibility
Incorrect installation, adjustment, and
use of this burner could result in severe
personal injury, death, or substantial
property damage from re, carbon
monoxide poisoning, soot or explosion.
Contact a professional, quali ed service agency for the
installation, adjustment and service of your oil heating
system. This work requires technical training, trade
experience, licensing or certi cation in some states and
the proper use of special combustion test instruments.
Please carefully read and comply with the following
instructions:
y Never store or use gasoline or other ammable liquids
or vapors near this burner or appliance.
y Never attempt to burn garbage or refuse in this
appliance.
y Never attempt to light the burner/appliance by throwing
burning material into the appliance.
y Never attempt to burn any fuel not speci ed and
approved for use in this burner.
y Never restrict the air inlet openings to the burner or
the combustion air ventilation openings in the room.
Impaired Burner Performance
and Fire Hazard.
Do NOT operate the burner beyond speci cations
outlined in the table to the right.
y For applications beyond these limits, consult Beckett
Technical Service at 1-800-645-2876.
y NOTE: Some packaged appliances with burners
may be agency listed as a unit to operate beyond
these limits. Consult the appliance manufacturer’s
speci cations and agency approvals for veri cation.
Prepare Before Installing
Notice Special Requirements
If you discover damage to the burner
or controls during unpacking, notify
the carrier at once and le the appropriate claim.
When contacting Beckett for service
information — Please record the
burner serial number (and have available when calling or
writing). You will nd the serial number on the silver label
located on the left rear of the burner. See Figure 1.
Speci cations
Capacity ‘F’ Head
Firing Rate: 0.75 - 2.50 GPH
Input: 105,000 - 350,000 Btu/h
Fuels USA: No. 1 or No. 2 diesel fuel or kerosene;
No.1 or No. 2 heating oil (ASTM D396)
DO NOT USE GAS-
OLINE, CRANKCASE OIL, OR ANY
OIL CONTAINING GASOLINE.
Electrical Power Supply: 13.5 Vdc
Operating Load
w/ igniter on: 15 Amps
w/ igniter off: 8 - 10 Amps
Motor: 13.5Vdc, 1/6 hp, 3450 RPM, 10
Amps (max.) NEMA “M” Flange, rotation
CCW when facing shaft end.
Ignition Secondary: 20KVpk 25mA
Interrupted duty OR optional continuous
duty.
Pump Outlet pressure: Note 1
Dimensions Height (maximum): 11 ½ inches
Width (maximum): 14 3/8 inches
Depth (chassis only): 6 9/16 inches
Air tube diameter: 4 inches
Ambient
Operating
Temperature
+32° F. (0° C.) Minimum
+115° F. (+46° C.) Maximum
(See Warning on Impaired Burner
Performance and Fire Hazard.)
Note 1. See equipment manufacturer’s burner speci cations
for recommended outlet pressure. Pressure is 100 psig unless
otherwise noted.