Mobile Home Requirements
Outside air must be installed - see "Outside Air Requirements" on page 11
Chimney connector and chimney must be one of the following types:
AMERI-TEC model DCC connector with AMERI-TEC UL 103 HT chimney
DURAVENT model DVL connector with DURAVENT UL 103 HT chimney
I.C.C. Excel HP connector with I.C.C. UL 103 HT chimney
METALFAB model DW connector with METALFAB UL 103 HT chimney
SECURITY model DP connector with SECURITY UL 103 HT chimney
Standard Masonry Chimney with any one of the above listed connectors
NOTE: Reduced clearance connectors may not connect to the flue collar – an appliance adapter may be required.
Stove placement must maintain the following clearances to combustibles (drywall, furniture, etc.)
Straight Installations
a
b
d
e
Corner Installations
c
f
NOTE:
Measure clearances to the stove top.
Figure 8
Minimum Clearance
(See the illustration above)
Reduced Clearance
Connector
A Sidewall to stove 16"
B Backwall to stove 10"
C Cornerwall to stove 7-1/2"
D Connector to sidewall 27-1/4"
E Connector to backwall 12-1/4"
F Connector to cornerwall 18-1/2"
If using offsets, use the connector clearance listed in Figure 9,
not the connector manufacturer's clearance.
The appliance must be secured to the floor (consult your building
official). Secure the outside air boot to the floor and stove to
insure the stove does not dislocate.
Mobile home installations require a spark arrester at the chimney
termination.
The appliance must be grounded to the chassis of the mobile
home (consult your building official).
WARNING:DO NOT INSTALL IN SLEEPING ROOM.
CAUTION:THE STRUCTURAL INTEGRITY OF THE MOBILE
HOME FLOOR, WALL, AND CEILING/ROOF MUST BE
MAINTAINED.
Minimum Stove
Clearance
(as outlined above)
12-1/4
Min.
Minimum Connector
Clearance
(as outlined above)
Figure 9