G8000 Series with Isolated Output Installation and Operation Manual
12.3 Electrical Specication
AC Input Rated Capacity 100 kVA (80 kW) 150 kVA (120 kW)
Input Voltage 480 V ( +10% – -15% ),
3-Phase 3-Wire
Input Frequency 60 Hz ±5%
Input Power Factor 1.00 – 0.95 Lagging ( at 100% Load )
Current Harmonic Distortion 5% Maximum ( at 100% Load )
Input Capacity Required 107 kVA 154 kVA
Circuit Breaker Rating At 480 V Input 200 A 250 A
DC Input Rated Capacity 100 kVA (80 kW) 150 kVA (120 kW)
Voltage Window 288 – 414 V
Recharge Voltage Regulation ± 1.5%
AC Output Rated Capacity 100 kVA (80 kW) 150 kVA (120 kW)
Output Voltage 208/120 V ± 1%, 3-Phase 4-Wire
Output Power Factor 0.8 Lagging
Voltage Distortion 3% with 100% Linear Load / 5% with Non-Linear
Load
Transient Voltage Regulation < ± 2%
Transient Settling Time < 50 msec
Crest Factor < 2.0
Output Frequency 60 Hz ± 0.01% ( at Free-running Mode)
Synchronous Window To Utility Line 59 Hz – 61 Hz
Frequency Slew Rate 1 Hz/Sec
Over Load Rating 100%-Continuous / 125%-10min. / 150%-1min.