G8000 Series with Isolated Output Installation and Operation Manual
Cable knockout plates are provided at the bottom of the 100 kVA UPS, and at the bottom and top of the 150
kVA UPS. The recommended hole locations are illustrated in Figure 11.4 - 11.6
The ve (5) holes must be punched during installation. The dashed rectangle indicates the UPS opening
behind the knockout plates.
FIGURE 11.4 - BOTTOM CABLE KNOCKOUT PLATES - 100 KVA)
FIGURE 11.5 - BOTTOM CABLE KNOCKOUT PLATES - 150 KVA
FIGURE 11.6 - TOP CABLE KNOCKOUT PLATE - 150 KVA
11.2 External Breakers
The G8000 UPS units are not equipped with circuit breakers. Qualied personnel should provide the
external breakers for the AC input/output, bypass input and DC input.
See Figure 11.1 – External Wiring Diagram, for the circuit position of the breakers.
Table 11.3 shows the G8000 UPS minimum external breaker rating for each capacity. The bypass input and
the AC output require 3-pole breakers.
TABLE 11.3 EXTERNAL BREAKER RATING
Capacity
AC Input / Bypass Input / AC Output
Minimum Breaker Rating
DC Input
Minimum Breaker Rating
100 kVA 480V - 200A / 480V - 200A / 208V - 350A 500 VDC – 400 A
150 kVA 480V - 250A / 480V - 250A / 208V - 600A 500 VDC – 600 A
G8000 Series Installation Manual
30
CONTROL
WIRES
0.8”
0.8”
2” Dia.
3” Dia.
AC INPUT
C OUTPUT
BATTERY
Plate #2
Plate #1
1 2 3 64 5 7 8 9 10 11 12
AC INPUT
3-phase 3-wire
BYPASS INPUT
3-phase 4-wire
BATTERY
AC OUTPUT
3-
hase 4-wire
U V W
- +
U V WVUNW
The cable knockout plates are provided at the bottom of each 100/150/225kVA UPS. The recommended
hole locations are illustrated in Figure 11.3 and 11.4.
The five (5) holes must be punched during installation. The dashed rectangle indicates the UPS opening
behind the knockout plates.
FIGURE 11.3 - CABLE KNOCKOUT PLATES100kVA (T80S3K10KK6XS2H
)
FIGURE 11.4 - CABLE KNOCKOUT PLATES
100kVA (T80S3K10KK6XSNH
); 150/225kVA
The terminal busses are located inside at the top of the 300kVA UPS. See Figure 11.5. The dashed line
indicates the side view of the bolt holes. Use 1/2 inch bolts to attach the lugs.
See Table 11.6 for recommended cable size and tightening torque for the 300kVA UPS. See Table 11.7
for vendor recommended lugs.
FIGURE 11.5 - TERMINAL BUSSES OF THE 300kVA UPS
0.4”
0.8”
BATTERY
CONTROL
WIRES
Plate #1
Plate #2
Plate #3
PLATE #1 PLATE #2
G8000 Series Installation Manual
30
CONTROL
WIRES
0.8”
0.8”
2” Dia.
3” Dia.
AC INPUT
C OUTPUT
BATTERY
Plate #2
Plate #1
1 2 3 64 5 7 8 9 10 11 12
AC INPUT
3-phase 3-wire
BYPASS INPUT
3-phase 4-wire
BATTERY
AC OUTPUT
3-
hase 4-wire
U V W
- +
U V WVUNW
The cable knockout plates are provided at the bottom of each 100/150/225kVA UPS. The recommended
hole locations are illustrated in Figure 11.3 and 11.4.
The five (5) holes must be punched during installation. The dashed rectangle indicates the UPS opening
behind the knockout plates.
FIGURE 11.3 - CABLE KNOCKOUT PLATES100kVA (T80S3K10KK6XS2H
)
FIGURE 11.4 - CABLE KNOCKOUT PLATES
100kVA (T80S3K10KK6XSNH
); 150/225kVA
The terminal busses are located inside at the top of the 300kVA UPS. See Figure 11.5. The dashed line
indicates the side view of the bolt holes. Use 1/2 inch bolts to attach the lugs.
See Table 11.6 for recommended cable size and tightening torque for the 300kVA UPS. See Table 11.7
for vendor recommended lugs.
FIGURE 11.5 - TERMINAL BUSSES OF THE 300kVA UPS
0.4”
0.8”
BATTERY
CONTROL
WIRES
Plate #1
Plate #2
Plate #3
PLATE #2 PLATE #3PLATE #1
4” Dia.