14
G8000 Series with Isolated Output Installation and Operation Manual
6 Warning Labels
Below are representative warning labels and their location on the UPS. Exterior Handling labels shown
in section 4.3, Transporting/Unpacking, are in the manual packet, and attached to the UPS shipping
covering and shipping pallet.
ATTENTION
Make sure all the warning labels are installed in the appropriate locations.
If a label is missing or illegible, contact Toshiba Customer Support Center or an
authorized representative.
DANGER
AC VOLTAGE
This UPS receives power from more
than one source. Disconnect all AC
sources before performing any service
or testing inside this unit
48082
DANGER
Hazardous voltages are used in the operation
of this equipment and could cause severe personal
injury or loss of life.
The following precautions should be observed to
reduce the risk of injury or death.
HAZARDOUS VOLTAGES
Only qualified technicians familiar with this equipment and the
information supplied with it should be permitted to install and
operate this equipment.
Installation of electrical equipment must be done in
accordance with National Electrical Code and any other state
or local codes. Proper grounding and conductor sizing must
be installed for safe operation.
During operation, keep all covers in place and cabinet
doors shut.
When performing visual inspections and maintenance, if
possible, be sure the UPS is turned off and the incoming
AC feed is turned off and locked out.
If it is necessary to make measurements with the power
on, do not touch any electrical connection points. Remove
all jewelry from wrists and fingers. Make sure test equipment
is in good, safe operating condition.
While servicing, stand on some type of insulation, and be
sure not to be grounded.
Follow the safety instructions given in the equipment manual
carefully and observe all danger, warning and caution notices.
40308
The UPS and Battery Cabinet will have hazardous
voltages present even after the AC feed is turned off.
PN 40830
Incorrect fuse replacement size
may result in fire or inadequate
equipment protection.
Replace only with same type
and rating of fuse.
CRITICAL FUSE SIZING
WA RNING
(A) – 48082 (B) – 40308
(C) – 59940 for 100 and 150 kVA
(D) – 40830