G8000 Series with Isolated Output Installation and Operation Manual
12 UPS Specications
12.1 General Specication
Terms Specication Remarks
Conforming Standard UL1778-2001 UL, cUL, IEC
Ambient Temperature 32 – 104 °F (0 – 40 °C)
Relative Humidity 30% – 90% Non-condensing
Altitude
< 3,280 ft (< 1,000 m) Contact Toshiba Technical Support for
instalation above 3280 ft. (1000 m)
Audible Noise 68dB(150 kVA) 1m (39”) away from front
Insulation Resistance 3 MΩ With 500 V-Megger
Insulation Breakdown
AC 2 kV – 1 min. Main Circuit
AC 1.5 kV – 1 min. External Interface
AC 500 V – 1 min. Control Circuit
12.2 Mechanical Specication
Rated Capacity 100kVA
Cabinet
Protection
Conformity
IEC298 IP20*
Exterior Paint Sherwin Williams, HHT2-7055, 079 Beige Texture
Panel Thickness
FRONT: 1/16 in. (1.6mm)
BACK/SIDE/TOP: 3/64 in. (1.2mm)
BOTTOM: 1/8 in. (3.2mm)
Input/Output
Cabling Entrance
BOTTOM
Ground/Control
Wiring Entrance
BOTTOM
Outline
Dimension
W: 36.8 in. (935 mm)
D: 31.8 in. (808 mm)
H: 79.2 in. (2,012 mm)
Unit Weight 2006 lb (1000 kg))
Shipping Weight 2096 lb (1041.4 kg)
Floor Loading
Per Footprint
2446 lbs/ft
2
(13,126 kg/m
2
)
Clearance
FRONT: 43 7/16 in. (1,100 mm)
BACK/SIDE: 0 in. (0 mm)
TOP: 15 3/4 in. (400 mm)
Heat Rejection
27,620 BTU/h
(6,960 kcal/h)
*IP20: Foreign objects that are 12mm (15/32”) or larger are prevented from entering the enclosure of the UPS.