G8000 Series with Isolated Output Installation and Operation Manual
Be trained and authorized to safely energize, de-energize, ground, lockout/tagout circuits and equipment, and clear
faults in accordance with established safety practices.
Be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves, hard hats, safety
glasses, face shields, ash clothing, etc., in accordance with established safety practices.
Be trained in rendering rst aid.
For further information on workplace safety visit www.osha.gov.
2.4 Factory Authorized Personnel
Factory authorized personnel have been factory trained and certied to install, service, and repair the UPS. Contact the
Toshiba Customer Support Center for assistance in locating the factory authorized personnel nearest you.
3 Important Safety Instructions
The following contains important instructions that should be followed during the installation, operation, and maintenance of
the G8000 Series UPS.
Please refer to the battery manufacturer’s instructions for details on operating, maintaining and/or replacing the batteries
for each system. Unauthorized personnel from batteries. Only a factory authorized representative with battery experience
should perform service on batteries.
CAUTION
Misuse of this equipment could result in personal injury and/or equipment damage.
In no event will Toshiba Corporation be responsible or liable for either indirect or
consequential damage or injury that may come from the use of this equipment.
The UPS system input and output is NOT equipped with an over-current protection device, or an output disconnection
at the AC output. The user should provide circuit breakers between the UPS AC input (or Bypass input) and the power
sources and between the UPS output and the critical load input. The minimum device ratings are listed in Table 3.1.
TABLE 3.1 UPS MINIMUM DEVICE RATINGS
CapaCity Rated Output input BReakeR Rating Output BReakeR Rating
100 kVA 208/120 Vac 480V-200 A 208V-350 A
150 kVA 208/120 Vac 480V-250 A 208V-600 A
The maximum operating ambient temperature should be 40 °C (104 °F). If the UPS is exposed to the same ambient
temperature as the battery system, the maximum operating ambient temperature should be 32 °C (90 °F). Table 3.2 lists
the nominal battery voltage.
TABLE 3.2 UPS NOMINAL BATTERY VOLTAGE
CapaCity nOminal VOltage FlOat VOltage
100 kVA 360 Vdc 405 V
150 kVA 360 Vdc 405 V