Setting Up the Drive 3-19
Setting up and using Macro 2
The following may require attention in addition to
the settings made in Chapter 2.
Motorized potentiometer settings
1. By default, the Drive operates in frequency
control. To disable this and enable the
motorized potentiometer, close the MOT. POT.
ENABLE contact (terminal 29).
2. If required, change the value of 0.29 Motorized
pot. rate to change the rate of increase and
decrease. Increasing the value reduces the rate
of change of frequency.
Default value: 20 s
Range: 0 ~ 250 s
3. If bipolar operation is required, set 0.28
Motorized pot. bipolar select at 1.
4. By default, every time the Drive is powered-up
and enabled, the frequency will return under
ramp control to the last setting of the
motorized potentiometer. If the Drive is
required to start at zero, set 0.27 Motorized
pot. zero-start select at 1.
5. To reset the motorized potentiometer,
momentarily close the RESET contact. (This
also resets the Drive.)
6. If required, change the scaling of the
motorized potentiometer output by adjusting
0.30 Motorized pot. output scale factor.
7. If required, monitor the output value of the
potentiometer by reading 0.26 Motorized pot.
output indicator.
Reference selection
For correct operation of this macro configuration,
the setting of parameter of 0.05 Reference selection
should be at 0.
Analog input modes
The analog input can be configured for the
following input signals:
0 ~ 20mA, 4 ~ 20mA or 0 ~ 10V
Refer to the following parameter in Appendix D
Menu 0 Parameters for selecting the required mode:
Analog
input
Terminal(s) Parameter
1 5, 6
0.24
Analog input 1 mode selector
Jog frequency
There is no need to adjust 0.14 Jog reference since
the jog function cannot be used.
Stopping and braking modes
Refer to the following parameters in Appendix D
Menu 0 Parameters:
Parameter
Setting
Function
0.150.15
Ramp mode selector
Stnd.Ct
(Standard controlled)
Deceleration time is
extended if the
DC-bus
voltage reaches its
maximum permissible
value during braking.
0.160.16
Stop mode selector
rP
Ramp to stop then the
Drive is disabled