Yukon Advanced Optics Oil Furnace Furnace User Manual


 
31
Questions? Visit www.yukon-eagle.com or call 1-800-358-0060
Operating Instructions
OIL FIRING THE UNIT
To start the oil burner on a new installation
1. Check to make sure there is oil in the storage tank.
No. 2 fuel oil may be used if tank is in the basement
or buried below ground. No. 1 fuel oil is
recommended if the tank is outside and above
ground.
2. The oil burner was started and tested at the factory.
Double check to make sure the proper oil burner
nozzle is installed and electrodes are set according
to the oil burner manual.
3. Turn oil tank valve lever to ON.
4. The furnace should be connected to a 110-Volt, 20
Amp circuit protector (fuse or circuit breaker.) Turn
switch to “ON”.
5. Set burner thermostat 10 degrees higher than room
temperature. If the furnace is connected to the oil
tank with a single line, air may have to be purged to
the burner. (See burner manual). If there is no air in
the oil line, the burner will start. If air is in the oil line,
the cad cell will not see a flame and shut down. Wait
5 minutes and turn back on. The correct pump
pressure of 100 psi was set at the factory. The draft
regulator that is connected to the chimney pipe must
be set a .03” Water Column negative to the chimney
with the burner operating at least 5 minutes.
6. Refer to burner manual for service tips.
STARTING BURNER AFTER IGNITION FAILURE
Before proceeding, find the cause of ignition failure. It
may be a plugged nozzle, dirty electric eye, soot on
electrodes, air in the line, or plugged oil line. Do not
attempt to restart burner when excess oil has
accumulated or if the combustion chamber is
very hot. Press the reset button on primary relay control
and burner should start. Do not attempt this more
than twice. If burner fails to operate, call a service
technician.
FIG. 29
WAYNE MODEL MSR
OIL BURNER