Yukon Advanced Optics Oil Furnace Furnace User Manual


 
Installation
Questions? Visit www.yukon-eagle.com or call 1-800-358-0060
26
INSTALLATION
Install barometric draft control using a 24 or 26 gauge
8” X 8” X 8” galvanized or black sheet metal Tee.
Use Spirit Level to make sure that the control does not
lean forward or backward but instead is plumb in both
directions, regardless of whether the flue is horizontal,
vertical or sloping.
INITIAL SETTING OF BAROMETRIC CONTROL
Set the control at a maximum of .03 or as low a draft as
will give good combustion and meet the requirements
for heat. Turn adjustment weight counter-clockwise to
loosen, then slide in slot to proper position and tight.
Bracket is marked 2, 4, 6, and 8, which indicates draft
setting of .02, .04, etc. (These are drafts in flue adjacent
to control, not over-fire drafts.
DO NOT ATTACH DRAFT
CONTROL TO TOP OR
BOTTOM OF FLUE PIPE,
NOR IN ROOM SEPARATED
FROM APPLIANCE.
BEST LOCATION IS AS
CLOSE TO APPLIANCE AS
POSSIBLE.
IMPORTANT:
MAKE THESE ADJUSTMENTS WHEN INSTALLING.
VERTICAL FLUE:
Adjustment weight must be in RIGHT HAND SLOT
(Marked “V”) in bracket on gate.
The arrow on flap at bottom of gate must line up with
letter “V” on lower right part of gate. If it does not,
remove flap, turn over and snap on to gate again.
Flap can be removed by inserting small screw driver at
the back side of the gate between the gate and the flap,
then pulling downward on flap.
HORIZONTAL FLUE:
Adjustment weight must be in LEFT HAND SLOT
(Marked “H”) in bracket on gate.
The arrow on flap at bottom of gate must line up with
letter “H” on lower left part of gate. If it does not, remove
flap, turn over and snap on to gate again.
IMPORTANT
A MANOMETER MUST BE USED TO
ACCURATELY ADJUST FLUE DRAFT