York YHJF18 THRU 60 Heat Pump User Manual


 
510667-YTG-B-0509
2 Johnson Controls Unitary Products
All dimensions are in inches. They are subject to change with-
out notice. Certified dimensions will be provided upon request.
Physical and Electrical Data
MODEL
YHJF18
S41S1
YHJF24
S41S1
YHJF30
S41S1
YHJF36
S41S1
YHJF42
S41S1
YHJF48
S41S1
YHJF60
S41S1
Unit Supply Voltage 208-230V, 1 60Hz
Normal Voltage Range
1
187 to 252
Minimum Circuit Ampacity 11.9 17.6 17.3 23.7 26.1 28.8 35.3
Max. Overcurrent Device Amps
2
20 30 30 40 45 50 60
Min. Overcurrent Device Amps
3
15 20 20 25 30 30 40
Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Compressor Amps
Rated Load 9.0 13.4 12.8 17.9 19.8 28.8 35.3
Locked Rotor 48.0 58.3 64.0 96.7 115.0 115.0 118.0
Crankcase Heater No No No No No No No
Fan Motor Amps Rated Load 0.7 0.8 1.3 1.3 1.3 1.3 1.3
Fan Diameter Inches 24 22 24 24 24 24 24
Fan Motor
Rated HP 1/10 1/8 1/4 1/4 1/4 1/4 1/4
Nominal RPM 825 1075 850 850 850 850 850
Nominal CFM 2000 2000 3900 3900 3900 3800 3800
Coil
Face Area Sq. Ft. 15.72 19.17 23.58 23.58 23.58 23.58 23.58
Rows Deep 1111122
Fin / Inches 22 22 22 22 22 18 18
Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Vapor Line Set OD (Field Installed) 3/4 3/4 3/4 3/4 7/8 7/8 1-1/8
Unit Charge (Lbs. - Oz.)
4
6 – 15 7 – 14 9 – 14 10 – 9 10 – 9 14 – 2 14 – 2
Charge Per Foot, Oz. 0.62 0.62 0.62 0.62 0.67 0.67 0.75
Operating Weight Lbs. 145 145 176 193 198 248 290
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add
or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
B
C
A
Unit
Model
Dimensions
(Inches)
Refrigerant Connection
Service Valve Size
A
1
1. Including Fan Guard.
B C Liquid Vapor
18
28 34 34
3/8”
3/4”
24 40 29 29
30 40 34 34
36 40 34 34
42 40 34 34
7/8”48 40 34 34
60 40 34 34