Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
HIGH CFM
COOLING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATION
CONDENSING UNIT MODEL NO. YHJF60S41S1
INDOOR COIL MODEL NO. AHX60
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 1650 1850 2050
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 56.5 60.0 59.6 65.6 70.6 58.5 61.2 60.8 66.7 72.5 60.5 62.3 62.0 67.8 74.4
S.C. 55.7 50.3 42.9 42.5 34.9 57.7 53.1 44.9 44.5 36.0 59.6 55.9 47.0 46.5 37.1
KW 3.4 3.5 3.5 3.5 3.6 3.5 3.6 3.5 3.6 3.7 3.6 3.6 3.6 3.7 3.8
75
T.C. 54.4 57.2 56.8 62.6 67.6 56.3 58.2 57.9 63.6 69.1 58.1 59.2 59.0 64.6 70.6
S.C. 53.6 49.1 41.6 41.3 33.5 55.4 51.9 43.7 43.2 34.6 57.3 54.7 45.7 45.2 35.7
KW 3.8 3.9 3.8 3.9 4.0 3.9 3.9 3.9 4.0 4.1 4.0 4.0 4.0 4.1 4.2
85
T.C. 52.3 54.4 54.0 59.6 64.6 54.0 55.2 55.0 60.5 65.8 55.7 56.1 56.0 61.3 66.9
S.C. 51.5 48.0 40.3 40.1 32.2 53.2 50.7 42.4 42.0 33.2 54.9 53.4 44.4 43.9 34.3
KW 4.2 4.2 4.2 4.3 4.4 4.3 4.3 4.3 4.4 4.5 4.4 4.4 4.4 4.5 4.6
95
T.C. 50.2 51.6 51.2 56.5 61.7 51.8 52.3 52.1 57.3 62.4 53.3 52.9 53.0 58.1 63.2
S.C. 49.5 46.8 39.1 38.9 30.8 51.0 49.5 41.1 40.8 31.8 52.5 52.1 43.1 42.6 32.9
KW 4.6 4.6 4.6 4.7 4.8 4.7 4.7 4.7 4.8 4.9 4.8 4.8 4.8 4.9 5.0
105
T.C. 47.5 48.0 47.8 52.6 57.5 48.8 49.0 48.4 53.3 58.1 50.2 50.0 49.1 54.0 58.8
S.C. 46.8 45.2 37.6 37.4 29.2 48.1 47.3 39.6 39.2 30.2 49.5 49.3 41.5 41.1 31.3
KW 5.1 5.1 5.1 5.2 5.3 5.2 5.2 5.2 5.3 5.4 5.3 5.3 5.3 5.4 5.5
115
T.C. 44.7 44.4 44.4 48.7 53.3 45.9 45.7 44.8 49.3 53.9 47.1 47.1 45.2 49.8 54.4
S.C. 44.1 43.7 36.1 35.8 27.6 45.2 45.0 38.0 37.7 28.6 46.4 46.4 39.9 39.5 29.7
KW 5.6 5.6 5.6 5.7 5.8 5.7 5.7 5.7 5.8 5.9 5.8 5.8 5.8 5.9 6.0
125
T.C. 42.0 40.7 41.0 44.8 49.2 43.0 42.5 41.1 45.3 49.6 44.0 44.2 41.3 45.7 50.0
S.C. 41.4 40.7 34.6 34.3 26.0 42.3 42.5 36.5 36.2 27.0 43.3 43.5 38.4 38.0 28.1
KW 6.1 6.1 6.1 6.2 6.3 6.2 6.2 6.2 6.3 6.4 6.3 6.3 6.3 6.4 6.5
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil T.C. S.C. KW
MV20D FC/MC62D 1.03 1.01 0.96
Furnace Coil T.C. S.C. KW
T*(8,L)X*C20 FC/MC62D 1.02 0.97 0.93
T*9X*C20 FC/MC62D 1.01 0.95 0.93
T*9X*D20 FC/MC62D 1.02 0.97 0.93
Y*(8,L)C*C20 FC/MC62D 1.01 0.96 0.93
(Y*9C/T*9V)*C20 FC/MC62D 1.01 0.96 0.96
(Y*9C/T*9V)*D20 FC/MC62D 1.01 0.96 0.95