York YHJF18 Air Conditioner User Manual


 
510667-YTG-A-0409
Johnson Controls Unitary Products 15
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. YHJF36S41S1
INDOOR COIL MODEL NO. AHX36
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 1000 1200 1400
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 34.5 36.4 37.1 40.1 42.7 36.2 37.6 37.8 41.2 43.4 38.0 38.7 38.5 42.3 44.1
S.C. 34.5 36.4 32.5 32.1 26.5 36.2 37.6 34.8 34.5 27.5 38.0 38.7 37.1 36.9 28.4
KW 1.9 2.0 2.0 2.0 2.0 2.0 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.2 2.2
75
T.C. 33.0 34.5 34.9 38.1 41.1 34.7 35.6 35.7 39.2 41.7 36.4 36.6 36.5 40.2 42.4
S.C. 33.0 34.5 31.4 31.1 25.5 34.7 35.6 33.8 33.5 26.5 36.4 36.6 36.1 35.9 27.5
KW 2.2 2.2 2.2 2.3 2.3 2.3 2.3 2.3 2.3 2.4 2.4 2.4 2.4 2.4 2.4
85
T.C. 31.5 32.6 32.8 36.2 39.4 33.2 33.6 33.6 37.1 40.0 34.9 34.5 34.4 38.1 40.6
S.C. 31.5 32.6 30.2 30.1 24.5 33.2 33.6 32.7 32.5 25.6 34.9 34.5 34.4 34.9 26.7
KW 2.4 2.5 2.5 2.5 2.6 2.5 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.7 2.7
95
T.C. 29.9 30.7 30.6 34.3 37.8 31.6 31.6 31.5 35.1 38.3 33.3 32.4 32.4 36.0 38.9
S.C. 29.9 30.7 29.1 29.2 23.4 31.6 31.6 31.5 31.5 24.6 33.3 32.4 32.4 33.9 25.8
KW 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.9 2.9 2.9 2.9 2.9 2.9 2.9
105
T.C. 28.2 28.1 28.0 31.8 35.3 29.8 29.4 28.9 32.6 35.9 31.4 30.8 29.7 33.4 36.6
S.C. 28.2 28.1 27.6 28.0 22.3 29.8 29.4 28.9 30.3 23.6 31.4 30.8 29.7 32.7 24.8
KW 3.0 3.0 3.0 3.0 3.1 3.1 3.1 3.1 3.1 3.2 3.2 3.2 3.2 3.2 3.2
115
T.C. 26.5 25.5 25.3 29.4 32.7 28.0 27.3 26.2 30.1 33.5 29.5 29.2 27.1 30.9 34.2
S.C. 26.5 25.5 25.3 26.8 21.2 28.0 27.3 26.2 29.2 22.5 29.5 29.2 27.1 30.9 23.8
KW 3.3 3.3 3.3 3.3 3.3 3.4 3.4 3.4 3.4 3.4 3.5 3.5 3.4 3.5 3.5
125
T.C. 24.7 22.9 22.6 27.0 30.2 26.2 25.2 23.6 27.7 31.0 27.6 27.6 24.5 28.3 31.9
S.C. 24.7 22.9 22.6 25.6 20.1 26.2 25.2 23.6 27.7 21.4 27.6 27.6 24.5 28.3 22.7
KW 3.5 3.5 3.5 3.6 3.6 3.6 3.6 3.6 3.7 3.7 3.8 3.7 3.7 3.7 3.8
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil T.C. S.C. KW
AHX42 1.01 1.01 1.03
AV*36 1.00 0.99 1.06
F6FP042 1.02 1.04 1.03
MV12B FC/MC43B 1.00 1.00 1.06
MV16C FC/MC43C 0.99 0.99 1.05
Variable Speed
Furnace
Coil T.C. S.C. KW
T*(8,L)X*A12 FC/MC/PC37A 1.01 1.03 1.07
T*(8,L)X*B12 FC/MC/PC43B 1.01 1.03 1.07
T*(8,L)X*C16 FC/MC/PC43C 1.00 0.99 1.02
T*(8,L)X*C20 FC/MC/PC43C 1.02 1.03 1.03
T*9X*B12 FC/MC/PC43B 1.01 1.03 1.07
T*9X*C16 FC/MC/PC43C 1.02 1.03 1.08
T*9X*C20 FC/MC/PC43C 0.99 0.99 1.05
Y*(8,L)(C,V)*C16 FC/MC/PC43C 0.99 0.99 1.02
Y*(8,L)(C,V)*C20 FC/MC/PC43C 0.99 0.99 1.05
Y*9(C,V)*C16 FC/MC/PC43C 1.01 1.02 1.06
Y*9(C,V)*C20 FC/MC/PC43C 0.99 0.99 1.05