036-21137-004 Rev. C (0505)
Unitary Products Group 15
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H2RC024S06
INDOOR COIL MODEL NO. G1FA036S17,21
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 600 800 1000
ID DB (°F) 85 80 75 85 80 75 85 80 75
ID WB (°F) 72 67 63 72 67 63 72 67 63
75
T.C. 25.4 24.2 22.5 25.6 24.5 23.2 25.8 24.9 23.9
S.C. 14.6 14.6 13.8 15.4 15.6 15.4 16.3 16.6 17.1
KW 1.61 1.60 1.59 1.61 1.60 1.59 1.62 1.61 1.60
85
T.C. 24.9 23.6 21.4 25.1 23.9 22.2 25.3 24.2 23.0
S.C. 14.8 14.7 13.8 15.9 16.1 15.6 17.0 17.5 17.5
KW 1.75 1.74 1.71 1.76 1.75 1.73 1.78 1.76 1.74
95
T.C. 24.4 23.0 20.3 24.6 23.2 21.2 24.8 23.5 22.2
S.C. 14.9 14.7 13.7 16.3 16.6 15.8 17.7 18.4 17.9
KW 1.90 1.88 1.84 1.92 1.89 1.86 1.93 1.90 1.88
105
T.C. 22.9 20.8 18.2 23.3 21.4 19.1 23.8 22.0 20.0
S.C. 14.5 13.8 12.9 16.3 16.0 15.0 18.1 18.1 17.2
KW 2.04 2.01 1.96 2.07 2.02 1.98 2.09 2.04 2.00
115
T.C. 21.3 18.6 16.2 22.0 19.5 17.0 22.8 20.5 17.7
S.C. 14.0 12.9 12.0 16.3 15.3 14.2 18.6 17.8 16.4
KW 2.19 2.13 2.08 2.22 2.16 2.10 2.25 2.18 2.12
125
T.C. 19.8 16.4 14.2 20.7 17.6 14.9 21.8 19.0 15.4
S.C. 13.5 12.0 11.1 16.3 14.6 13.4 19.1 17.5 15.6
KW 2.34 2.25 2.20 2.37 2.30 2.22 2.41 2.32 2.24
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
F2RP/F2FP024 0.99 1.01 1.00
F2RP/F2FP030 1.00 1.03 1.00
F2RC/F2FC024 0.98 1.01 1.00
F2RC/F2FC030 0.98 1.01 0.99
N1AHB0806 G2FD024(S,H)17 0.99 0.98 0.99
N1AHB0806 G2FD030(S,H)17 1.00 1.00 1.00
N1VSB12 G2FD024(S,H)17 0.99 1.05 0.92
N1VSB12 G2FD036(S,H)17 1.05 1.17 0.94
G1FA024S14,17 0.96 0.95 1.00
G1FA030S14 0.99 0.98 0.99
G1FA036S14 1.01 1.02 1.00
G1HD024 1.00 0.99 1.01
G1HD036 1.03 1.04 1.00
G1NA030S17K 1.00 1.00 1.00
G1NA030S21M 1.00 1.00 1.00
G1UA024S14,17 0.96 0.95 1.00
G1UA030S14 0.99 0.98 0.99
G1UA036S14 1.01 1.02 1.00
G1UA036S17,21 1.00 1.00 1.00
G2FD024(S,H)14,17 0.99 0.98 0.99
G2FD030(S,H)17 1.00 1.00 1.00
G2FD035(S,H)14 1.00 1.00 1.00
G2FD036(S,H)17 1.03 1.03 1.00
Variable Speed
Furnace
Coil
T.C. S.C. KW
P1DUA12V G1FA024S14 0.98 0.97 0.93
P1DUA12V G2FD024(S,H)14 1.00 1.00 0.92
P1XDB12V G2FD024(S,H)17 1.01 1.01 0.94
P1XUB12V G1FA024S17 0.98 0.98 0.93
P1XUB12V G2FD024(S,H)17 1.01 1.01 0.93