York D1HE/D1HG036 Air Conditioner User Manual


 
036-21216-003-A-0204
8 Unitary Products Group
TABLE 6: COOLING CAPACITIES - MODELS DHE/DHG 036 - 105°F - 115ºF
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
105°F
TOTAL
CAP.
1
MBH
POWER
INPUT
2
SENSIBLE CAPACITY
3
ENTERING DRY BULB, °F
CFM
WB
°F
86 83 80 77 74 71 68
1500 72 47.6 3.65 32.3 27.8 23.3 18.9 14.4 #N/A #N/A
67 42.5 3.56 39.0 34.5 30.0 25.6 21.1 16.6 12.1
62 38.0 3.49 38.0 38.0 36.6 32.1 27.6 23.1 18.7
57 37.4 3.54 37.4 37.4 37.4 32.9 28.5 24.0 19.5
1350 72 46.5 3.62 29.7 25.8 21.8 17.8 13.8 #N/A #N/A
67 41.6 3.53 36.0 32.0 28.0 24.0 20.1 16.1 12.1
62 37.1 3.46 37.1 36.6 34.1 30.1 26.1 22.2 18.2
57 36.5 3.52 36.5 36.5 35.2 31.2 27.2 23.3 19.3
1200 72 45.4 3.60 27.2 23.7 20.2 16.7 12.2 #N/A #N/A
67 40.6 3.51 33.0 29.5 26.0 22.5 19.0 15.5 12.0
62 36.2 3.44 36.2 35.2 31.7 28.2 24.7 21.2 17.7
57 35.7 3.49 35.7 35.7 33.0 29.5 26.0 22.5 19.0
1050 72 43.2 3.57 24.6 21.6 18.5 12.5 #N/A #N/A
67 38.7 3.48 29.9 26.9 23.8 20.8 17.8 14.7 11.7
62 34.5 3.41 33.9 32.1 29.0 26.0 23.0 19.9 16.9
57 34.0 3.47 34.0 32.9 30.3 27.2 24.2 21.2 18.1
900 72 41.1 3.54 22.0 19.4 16.8 14.3 11.7 #N/A #N/A
67 36.7 3.45 26.8 24.2 21.7 19.1 16.5 14.0 11.4
62 32.8 3.39 31.5 28.9 26.4 23.8 21.2 18.7 16.1
57 32.3 3.44 32.3 30.1 27.5 24.9 22.4 19.8 17.2
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
115°F
TOTAL
CAP.
MBH
POWER
INPUT
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
CFM
WB
°F
86 83 80 77 74 71 68
1500 72 43.6 3.85 30.4 26.0 21.5 17.0 12.5 #N/A #N/A
67 39.3 3.76 37.8 33.3 28.8 24.3 19.9 15.4 10.9
62 34.8 3.67 34.8 34.8 34.4 29.9 25.4 20.9 16.5
57 34.9 3.73 34.9 34.9 34.9 30.5 26.0 21.5 17.0
1350 72 42.9 3.83 28.0 24.0 20.0 16.0 12.0 #N/A #N/A
67 38.6 3.74 34.8 30.8 26.8 22.8 18.8 14.9 10.9
62 34.2 3.66 34.2 34.0 32.0 28.0 24.0 20.0 16.0
57 34.3 3.72 34.3 34.3 32.9 28.9 24.9 21.0 17.0
1200 72 42.2 3.82 25.5 22.0 18.5 15.0 11.5 #N/A #N/A
67 37.9 3.73 31.8 28.3 24.8 21.3 17.8 14.3 10.8
62 33.6 3.64 33.6 33.1 29.6 26.1 22.6 19.1 15.6
57 33.7 3.70 33.7 33.7 30.9 27.4 23.9 20.4 16.9
1050 72 40.1 3.78 22.9 19.9 16.9 13.8 10.8 #N/A #N/A
67 36.1 3.69 28.7 25.7 22.6 19.6 16.6 13.5 10.5
62 32.0 3.61 31.6 30.0 27.0 23.9 20.9 17.9 14.9
57 32.1 3.67 32.1 30.9 28.2 25.1 22.1 19.1 16.0
900 72 38.0 3.75 20.4 17.8 15.2 12.7 10.1 #N/A #N/A
67 34.2 3.66 25.6 23.0 20.4 17.9 15.3 12.7 10.2
62 30.3 3.58 29.5 26.9 24.4 21.8 19.2 16.7 14.1
57 30.4 3.64 30.4 28.0 25.4 22.9 20.3 17.7 15.2
1.
These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance
Table, multiply this value by 3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit
2.
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor
power input is 0.36kW. Refer to Tables 10 and 11 for the kW of the supply air blower motor.
3.
These capacities are gross ratings. For net capacity, determine the kW of the supply air blower from Tables 10 and 11, multiply this value
by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
NOMINAL RATING ALL SENSIBLE CAPACITY