TABLE 15: ELECTRICAL DATA - COOLING/ELECTRIC HEAT DHE036 & 048
MODEL
DHE
POWER
SUPPLY
HEATER
ACCESSORY
MODEL
NUMBER
SUPPLY
AIR
BLOWER
MOTOR
FLA
ELECTRIC HEATERS
TOTAL
UNIT
AMPACITY
AMPS
MAX.
FUSE
SIZE
1
AMPS
MAX.
SIZE
HACR
2
AMPS
kW STAGES
TOTAL
AMPS
036
208-3-60
2CE04500525
3
5.3
4.0 1 11.0 25.2 35 35
2CE04500725
4
5.6 1 15.6 26.2 35 35
2CE04501025 8.0 1 22.1 34.2 35 35
2CE04501525 11.9 2 33.1 48.1 50 50
2CE04502025 15.9 2 44.2 61.9 70 70
230-3-60
2CE04500525
4
5.3
5.3 1 12.7 25.2 35 35
2CE04500725
4
7.5 1 18.0 29.2 35 35
2CE04501025 10.6 1 25.5 38.5 40 40
2CE04501525 15.9 2 38.2 54.4 60 60
2CE04502025 21.2 2 51.0 70.4 80 80
460-3-60
2CE04500746
4
3.1
6.8 1 8.2 14.1 20 15
2CE04501046
4
10.1 1 12.1 19.1 20 20
2CE04501546
4
13.6 1 16.4 24.3 25 25
2CE04502046
4
19.5 2 23.5 33.2 35 35
048
208-3-60
2CE04500525
4
6.0
4.0 1 11.0 26.0 35 35
2CE04500725
4
5.6 1 15.6 26.9 35 35
2CE04501025 8.0 1 22.1 35.3 35 35
2CE04501525 11.9 2 33.1 48.8 50 50
2CE04502025 15.9 2 44.2 62.7 70 70
230-3-60
2CE04500525
4
6.0
5.3 1 12.7 26.0 35 35
2CE04500725
4
7.5 1 18.0 30.1 35 35
2CE04501025 10.6 1 25.5 39.4 40 40
2CE04501525 15.9 2 38.2 55.3 60 60
2CE04502025 21.2 2 51.0 71.2 80 80
460-3-60
2CE04500746
4
3.0
6.8 1 8.2 14.0 15 15
2CE04501046
4
10.1 1 12.1 18.9 20 20
2CE04501546
4
13.6 1 16.4 24.2 25 25
2CE04502046
4
19.5 2 23.5 33.1 35 35
1.
Dual element, time delay type.
2.
Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
3.
These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago), refer to Table 17
for fuse block accessories available for field installation.
4.
These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago), refer to Table 17
for fuse block accessories available for field installation.
TABLE 16: ELECTRIC HEAT CORRECTION
FACTORS (DHE048)
NOMINAL VOLTAGE VOLTAGE
kW CAP
MULTIPLIER
208 208 1.00
240 230 0.92
480 460 0.92
600 575 0.92
TABLE 17: FUSE BLOCK ACCESSORY
2FB04700425 208/240 Volts
2FB04700546 460 Volts