York D1HE/D1HG036 Air Conditioner User Manual


 
036-21216-003-A-0204
Unitary Products Group 7
TABLE 5: COOLING CAPACITIES - MODELS DHE/DHG 036 - 85°F - 95ºF
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
85°F
TOTAL
CAP.
1
MBH
POWER
INPUT
2
SENSIBLE CAPACITY
3
ENTERING DRY BULB, °F
CFM
WB
°F
86 83 80 77 74 71 68
1500
72 55.2 3.18 35.2 30.7 26.2 21.8 17.3 #N/A #N/A
67 49.1 3.13 41.7 37.2 32.8 28.3 23.8 19.4 14.9
62 44.7 3.05 44.7 43.6 39.1 34.6 30.1 25.7 21.2
57 42.4 3.05 42.4 42.4 42.4 37.9 33.4 29.0 24.5
1350
72 55.2 3.18 35.2 30.7 26.2 21.8 17.3 #N/A #N/A
67 49.1 3.13 41.7 37.2 32.8 28.3 23.8 19.4 14.9
62 44.7 3.05 44.7 43.6 39.1 34.6 30.1 25.7 21.2
57 42.4 3.05 42.4 42.4 42.4 37.9 33.4 29.0 24.5
1200
72 51.9 -3.15 30.0 26.5 23.0 19.5 16.0 #N/A
67 46.1 3.10 35.7 32.2 28.7 25.2 21.7 18.2 14.7
62 42.0 3.02 41.2 37.7 34.2 30.7 27.2 23.7 20.2
57 39.8 3.03 39.8 39.8 37.3 33.8 30.3 26.8 23-3
1050
72 49.4 3.12 27.3 24.3 21.2 182 15.2 #N/A
67 43.9 3.07 32.6 29.6 26.5 23.5 20.5 17.4 14.4
62 40.0 2.99 37.7 34.7 31.6 28.6 25.6 22.5 19.5
57 37.9 3.00 37.9 37.0 34.5 31.4 28.4 25.4 22.3
900
72 46.9 3.09 24.6 22.1 19.5 16.9 14.4 #N/A
67 41.7 3.04 29.5 26.9 24.4 21.8 19.2 16.7 14.1
62 38.0 2.96 34.2 31.6 29.1 26.5 23.9 21.4 18.8
57 36.0 2.97 36.0 34.2 31.7 29.1 26.5 24.0 21.4
AIR ON
EVAPORATOR
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
95°F
TOTAL
CAP.
MBH
POWER
INPUT
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
CFM
WB
°F
86 83 80 77 74 71 68
1500
72 51.5 3.44 34.1 29.7 25.2 20.7 16.2 #N/A #N/A
67 45.8 3.35 40.2 35.7 31.3 26.8 22.3 17.8 13.4
62 41.2 3.30 41.2 41.2 38.8 34.3 29.8 25.3 20.9
57 39.9 3.35 39.9 39.9 39.9 35.4 31.0 26.5 22.0
1350
72 50.0 3.41 31.5 27.5 23.6 19.6 15.6 #N/A #N/A
67 44.5 3.32 37.2 33.2 29.2 25.3 2 13 17.3 13.3
62 40.0 3.27 40.0 39.2 36.3 32.3 28.3 24.3 20.3
57 38.8 3.32 38.8 38.8 37.5 33.5 29.6 25.6 21.6
1200
72 48.6 3.38 28.9 25.4 21.9 18.4 14.9 #N/A ' #N/A
67 43.2 3.29 34.2 30.7 27.2 23.7 20.2 16.7 13.2
62 38.9 3.23 38.9 37.2 33.7 30.2 26.7 23.2 19.8
57 37.6 3.29 37.6 37.6 35.1 31.6 28.1 24.6 21.1
1050
72 46.4 3.36 26.2 23.2 20.2 17.2 14.1 #N/A #N/A
67 41.2 3.27 31.1 28.1 25.0 22.0 19.0 16.0 12.9
62 37.1 3.21 36.2 34.1 31.1 28.0 25.0 22.0 18.9
57 35.9 3.27 35.9 34.9 32.3 29.3 26.3 23.2 20.2
900
72 44.2 3.34 23.6 21.0 18.4 15.9 13.3 #N/A #N/A
67 39.3 3.25 28.0 25.4 22.9 20.3 17.7 15.2 12.6
62 35.4 3.20 33.5 30.9 28.4 25.8 23.2 20.7 18.1
57 34.2 3.25 34.2 32.1 29.5 27.0 24.4 21.8 19.3
1.
These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply
this value by 3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit
2.
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to Tables 10 and 11 for the kW of the supply air blower motor.
3.
These capacities are gross ratings. For net capacity, determine the kW of the supply air blower from Tables 10 and 11, multiply this value by 3.415
MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
NOMINAL RATING ALL SENSIBLE CAPACITY