York D1HE/D1HG036 Air Conditioner User Manual


 
036-21216-003-A-0204
Unitary Products Group 19
NOTE: DHG modes must be provided a 1” clearance
between any combustible material and the supply
air ductwork for a distance of 2 feet from the unit.
The products of combustion must not be allowed to accumu-
late with a confined space and recirculate. Locate unit so that
the vent air outlet hood is at least.
Three feet above any forced air inlet located within 10
horizontal feet (excluding those integral to the unit).
Four feet below, 4 horizontal feet from, or 1 foot above
any door or gravity air inlet into the building.
Four feet from electric meters, gas meters, regulators
and relief equipment.
FIGURE 9 - UNIT DIMENSIONS DHG UNIT
TABLE 20: CLEARANCES
FRONT
DHE UNITS 24”
DHG UNITS 32”
BACK
12” (Less Economizer)
36” (With Economizer or
Fixed Air/Motorized
Damper)
LEFT SIDE (Filter Access)
24” (Less Economizer)
36” (With Economizer)
RIGHT SIDE (Cond. Coil) 24”
BELOW UNIT
1
1.
Units may be installed on combustible floors made from
wood or class A, B, or C roof covering material.
0”
ABOVE UNIT
2
2.
Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct condenser air dis-
charge outlet.
72” (For Condenser Air
Discharge)
R E T U R N A I R
S U P P L Y A I R
O U T D O O R A I R
O U T D O O R A I R
(
E c o n o m i z e r
)
All dimensions are in inches. They are
subject to change without notice. Certi-
fied dimensions will be provided upon
request.