York CZB018 THRU 060 Air Conditioner User Manual


 
246723-YTG-J-1006
4 Unitary Products Group
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of intercon-
necting line tubing.
2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the Physical and Electri-
cal Data Table.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
evaporator + adder for line set.
G1NA030S17K 563––––
G1NA030S21M 563––––
G1NA036S17J 563––––
G1NA036S21C 563––––
G1NA036S17L –––3–––
G1NA042S24W ––––6––
G1NA048S21D –––3–––
G1NA060S24T ––––612–
G1FA/G1UA024S14,17 5––––––
G1FA/G1UA030S14 5–3––––
G1FA/G1UA036S14 563––––
G1FA/G1UA036S17,21 563––––
G1FA/G1UA048S17 ––33–––
G1FA/G1UA048S21 ––33–––
G1FA/G1UA060S21,24 ––––6124
F*RP024/F*FP024 5––––––
F*RP030/F*FP030 –63––––
F*RP036/F*FP036 ––33–––
F*RP042/F*FP042 –––3–––
F*RP045/F*FP045 ––––6––
F*FP048 ––––6––
F*FP060 –––––––
F*FV060 –––––124
G4FD024H14,17 5––––––
G4FD030H17 563––––
G4FD035H14 563––––
G4FD036H17 5633–––
G4FD036H21 ––33–––
G4FD042H21 ––33–––
G4FD046H17 ––33–––
G4FD048H21,24 –––36––
G4FD060H24 –––––124
G4FD061H24 –––––124
G4FA024S14,17 5––––––
G4FA030S14 5––––––
G4FA036S14 563––––
G4FA036S17,21 563––––
G4FA048S17 ––33–––
G4FA048S21 ––33–––
G4FA060S21,24 ––––6124
FOOTNOTES:
1 Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
2 PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
Additional R-410A Charge / TXV Size for Various Matched Systems
Outdoor Unit
CZB01811 CZB02411 CZB03011 CZB03611 CZB04211 CZB04811 CZB06011
Unit Orifice (s)
1TVM901 1TVM903 1TVM903 1TVM903
1TVM904
1TVM4C1
1TVM905 1TVM905
Factory R-410A Charge, lbs-oz
5-13 6-4 7-4 6-4 8-13 8-12 13-9
Indoor Coil
1,2
Additional Charge, Oz