York CZB018 THRU 060 Air Conditioner User Manual


 
246723-YTG-J-1006
Unitary Products Group 3
Additional R-410A Charge / TXV Size for Various Matched Systems
Outdoor Unit
CZB01811 CZB02411 CZB03011 CZB03611 CZB04211 CZB04811 CZB06011
Unit Orifice (s)
1TVM901 1TVM903 1TVM903 1TVM903
1TVM904
1TVM4C1
1TVM905 1TVM905
Factory R-410A Charge, lbs-oz
5-13 6-4 7-4 6-4 8-13 8-12 13-9
Indoor Coil
1,2
Additional Charge, Oz
FC/MC/PC/UC18A3X 5––––––
FC/MC/PC/UC18B3X 5––––––
FC/MC/PC/UC24A3X 56–––––
FC/MC/PC/UC24B3X 56–––––
FC/MC/PC/UC30A3X 563––––
FC/MC/PC/UC30B3X 563––––
FC/MC/PC/UC36A3X ––33–––
FC/MC/PC/UC36B3X ––33–––
FC/MC/PC/UC36C3X ––33–––
FC/MC/PC/UC42B3X –––3–––
FC/MC/PC/UC42C3X –––3–––
FC/MC/PC/UC48C3X –––– 6––
FC/MC/PC/UC48D3X ––––6––
FC/PC/UC60C3X –––––124
FC/MC/PC/UC60D3X –––––124
MC61D3X ––––––4
HC18A3X 5––––––
HC30A3X –6–––––
HC36B3X ––33–––
HC42C3X –––––––
HC60D3X ––––6124
HD24A3X –––––––
HD36B3X ––33–––
HD48C3X ––––6––
HD60D3X –––––124
AHP18B3X 5––––––
AHP24B3X 56–––––
AHP30B3X ––3––––
AHP36C3X ––33–––
AHP42C3X –––3–––
AHP/SHP48D3X ––––612–
AHP/SHP60D3X ––––6124
AV24B3X 56–––––
AV36C3X ––33–––
AV/SV48D3X ––––6124
AV/SV60D3X ––––6124
G2FD024(S,H)14,17 5 –––––
G2FD030(S,H)17 563––––
G2FD035(S,H)14 563––––
G2FD036(S,H)17 5633–––
G2FD036(S,H)21 ––33–––
G2FD042(S,H)21 ––33–––
G2FD046(S,H)17 ––33–––
G2FD048(S,H)21,24 –––36––
G2FD060(S,H)24 –––––12 4
G2FD061H24 –––––12 4
G1HA024H14 56–––––
G1HA036H14 5––3–––
G1HA036H17 5 6 3 3–––
G1HA060H24 –––––124
G1HD024 56–––––
G1HD036 ––33–––
G1HD060 ––––––4
For Notes See Page 4