York CZB018 THRU 060 Air Conditioner User Manual


 
246723-YTG-J-1006
14 Unitary Products Group
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO. CZB03611
INDOOR COIL MODEL NO. G2FD036S17
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1050 1200 1350
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 32.7 33.4 31.9 34.6 38.3 34.4 34.2 32.1 35.6 38.5 36.1 34.9 32.4 36.6 38.7
S.C. 30.7 30.6 24.4 24.3 19.2 31.9 32.4 26.2 33.4 20.7 33.1 34.1 28.0 42.5 22.1
K.W. 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
75
T.C. 35.5 36.2 35.4 38.9 41.7 36.8 37.3 36.0 39.8 42.2 38.1 38.4 36.6 40.6 42.6
S.C. 33.7 31.3 26.3 26.3 21.1 35.1 33.5 28.0 20.8 22.1 36.6 35.6 29.8 15.4 23.2
K.W. 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
85
T.C. 34.1 34.8 33.6 36.7 40.0 35.6 35.7 34.0 37.7 40.3 37.1 36.6 34.5 38.6 40.7
S.C. 32.2 31.0 25.3 25.3 20.1 33.5 32.9 27.1 27.1 21.4 34.8 34.9 28.9 29.0 22.7
K.W. 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
95
T.C. 32.4 32.9 31.6 34.8 37.5 33.8 33.8 32.0 35.6 37.8 35.1 34.7 32.4 36.4 38.2
S.C. 30.5 29.7 24.4 24.6 19.4 31.8 31.4 26.1 26.3 20.6 33.0 33.1 27.8 28.0 21.8
K.W. 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
105
T.C. 30.7 31.0 29.5 32.9 35.1 31.9 31.9 30.0 33.5 35.4 33.1 32.8 30.4 34.2 35.6
S.C. 28.9 28.3 23.5 23.8 18.6 30.0 29.8 25.0 25.5 19.8 31.1 31.2 26.6 27.1 21.0
K.W. 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
115
T.C. 29.0 29.1 27.6 31.0 32.7 30.1 30.0 28.0 31.5 33.0 31.2 30.9 28.4 32.1 33.2
S.C. 27.3 27.0 22.6 23.0 17.8 28.3 28.2 24.0 24.6 19.0 29.3 29.5 25.5 26.2 20.2
K.W. 4.1 4.1 4.1 4.1 4.0 4.1 4.1 4.1 4.0 4.0 4.1 4.1 4.1 4.0 4.1
125
T.C. 27.4 27.2 25.6 29.1 30.3 28.3 28.2 26.0 29.5 30.5 29.3 29.1 26.4 29.9 30.8
S.C. 25.7 25.7 21.7 22.3 17.1 26.6 26.7 23.0 23.8 18.2 27.5 27.7 24.4 25.3 19.3
K.W. 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
MA12B FC/MC36B 1.00 1.00 1.00
MA12B FC/MC42B 1.01 1.00 1.00
MA12B G*FD046H17 1.01 1.00 1.00
MA14D G*FD048H24 1.01 1.00 1.00
MV12B MC36B 1.01 1.00 1.00
MV12B MC42B 1.01 1.01 1.00
AHP36 1.01 1.00 1.00
AHP42 1.01 1.00 1.00
AV36 1.01 1.00 0.95
F*FP036 1.01 1.01 1.00
F*FP042 1.02 1.01 1.00
FC/MC/PC/UC36 1.00 1.00 1.00
FC/MC/PC/UC42 1.01 1.00 1.00
G*FA048S17 1.01 1.00 1.00
G*FA048S21 1.01 1.00 1.00
G*FD036H21 1.01 1.00 1.00
G*FD042H21 1.01 1.00 1.00
G*FD046H17 1.01 1.00 1.00
G*FD048H21,24 1.01 1.00 1.00
HC36 1.01 1.00 1.00
HD36 1.00 1.00 1.00
Variable Speed
Furnace
Coil
T.C. S.C. KW
PV8*A12 FC/MC/PC36A 0.98 0.98 1.00
PV9*A12 FC/MC/PC36A 1.00 1.00 1.00
PV8*B16 FC/MC/PC36B 1.01 1.00 1.00
PV9*B12 FC/MC/PC36B 1.00 1.00 1.00
PV8*C16 FC/MC/PC36C 1.01 1.00 1.00
PV8*C20 FC/MC/PC36C 1.01 1.00 1.00
PV9*C16 FC/MC/PC36C 1.00 1.00 1.00
PV9*C20 FC/MC/PC36C 1.00 1.00 1.00
PV8*B16 FC/MC/PC42B 1.03 1.03 1.00
PV9*B12 FC/MC/PC42B 1.01 1.01 1.00
PV8*C16 FC/MC/PC42C 1.03 1.03 1.00
PV8*C20 FC/MC/PC42C 1.03 1.03 1.00
PV8*B16 HC36 1.01 1.00 1.00
PV9*B12 HC36 1.01 1.00 1.00
PV8*C16 HD36 1.01 1.00 1.00
PV9*C16 HD36 1.01 1.00 1.00
PV9*C20 HD36 1.01 1.00 1.00